Samson 5476 manual Appendix, Setting only possible after entering key number

Models: 5476

1 114
Download 114 pages 58.6 Kb
Page 86
Image 86
Manual background

Appendix

FB

Function

WE

Anl

Comments

 

36

BE8

 

All

FB36 to 43 = ON: Binary input in error status register

(12)

to

 

 

Select: StEIG: Fault indicated by rising edge/make contact

to

 

 

FALL: Fault indicated by negative edge/break contact

43

 

 

 

 

 

(19)

BE1

 

 

 

 

44

Modem operation

OFF

All

Select: 8-bit:

8-bit addressing

(20)

 

 

 

16-bit:

16-bit addressing

 

 

 

 

FB44 = ON: Modem function activated

 

 

 

 

Function block parameters:

 

 

 

 

Cyclical initialization In / 0 to 255 min (30 min)

 

 

 

 

Intervals between dialing PA / 0 to 255 min (5 min)

 

 

 

 

Modem timeout t0 / 0 to 99 min (5 min)

 

 

 

 

Dialing procedure/ PULS/ton (PULS)

 

 

 

 

Phone number of station GLT / 0 to 9, P, -; max. 23 characters

 

 

 

 

Setting only possible after entering key number!

45

Dial-up also upon

OFF

All

FB45 = ON: Dial-up when faults exist/remedied

(21)

corrected fault

 

 

FB45 = OFF: Dial up only when faults exist

 

 

 

 

Setting only possible after entering key number!

46

Phone number of

OFF

All

FB46 = ON: Dialing an alternative recipient

(22)

alternative recipient

 

 

Function block parameters:

 

 

 

 

Number of dialing attempts An / 0 to 99 (5)

 

 

 

 

Phone number of alternative recipient / 0 to 9, P, -; max. 23 char.

 

 

 

 

Setting only possible after entering key number!

47

Fault alarm output

OFF

All

FB47 = ON and FSr > 0: BA8 = ON

(23)

BA8

 

 

Pump management for UP1 no longer available

 

 

 

 

Setting only possible after entering key number!

FB Function block, WE Default setting, Anl System code number