Samson 5476 Limitation using 0/4 to 20 mA signal, Locking manual levels, System-widefunctions

Models: 5476

1 114
Download 114 pages 58.6 Kb
Page 62
Image 62
7.10.2 Limitation using 0/4 to 20 mA signal

System-wide functions

Functions

WE

Configuration

Current input for flow rate

OFF

FB22 = OFF

measurement

 

 

Flow rate or capacity limitation

OFF

FB23 = ON

 

500 pulse/h

Max. limit / 3 to 500 pulse/h

 

1.0

Limiting factor / 0.1 to 10

 

500 pulse/h

Max. limit for DHW / 3 to 500 pulse/h

 

1.0

Limiting factor / 0.1 to 10

7.10.2 Limitation using 0/4 to 20 mA signal

A connected heat meter (terminals GND/15 with a 50 Ω resistor connected in parallel) with a 0/4 to 20 mA output can be used to limit the flow rate in the system. All limit values are given in the unit “cubic meters per hour“ [m3/h]. As a result, it is necessary to se in addition to Lower measuring range value 0 or 4 mA also an Upper measuring range value (flow rate at which the 20 mA signal is issued) in unit [m3/h]. When the flow rate reaches the current Maximum limit , the controller switches in control circuit RK1 to flow rate control with the Maximum limit acting as the set point. If the flow temperature exceeds its normal set point by more than 5 °C during this time, the flow temperature control is started again. If the flow rate falls below the set Mini- mum limit, the control valve of control circuit RK1 is temporarily closed. The normal control op- eration is started again when the flow temperature falls below its normal set point by 5 °C.

Note!

In systems Anl 4 to 6 and 11, the valve of the heating circuit is affected during an active flow rate limitation.

Functions

WE

Configuration

Current input for flow rate measurement

OFF

FB22 = ON, select “Lower measuring range”

Flow rate or capacity limitation

OFF

FB23 = ON

 

10.00 m3/h Upper measuring range / 0.1 to 650 m3/h

 

0.01 m3/h Minimum limit/ 0.01 to 650 m3/h

 

9.00 m3/h

Maximum limit / 0.01 to 650 m3/h

7.11 Locking manual levels

The number of access options to the controller can be restricted by locking the manual level. When the locking is active, the mode switches positioned at the manual mode do not have any effect concerning manual activation of the valves. Merely, reactions occur as if the mode

62EB 5476 EN

Page 62
Image 62
Samson 5476 Limitation using 0/4 to 20 mA signal, Locking manual levels, System-widefunctions