Functions of the DHW circuit
6.3DHW heating with solar system (Anl 2, 3, 4, 5 und 9)
The systems Anl 2, 3, 4, 5 and 9 include a solar system for DHW heating. In these systems, the difference between the temperatures measured at storage sensor SF2 and the sensor at the so- lar collector CF is determined. The Solar pump ON parameter determines the minimum temper- ature difference between sensors SF2 and CF required to activate the solar pump. If the temper- ature difference falls below the value of Solar pump OFF, the solar pump is switched off. Ba- sically, the solar pump is also switched off when the water temperature measured at sensor SF2 has reached the Solar charging OFF parameter.
The
Function | WE | Configuration | ||
Storage tank sensor SF2 |
|
| FB15 = ON, select “CF“ | |
|
|
| ||
Parameters | WE | Range of values | ||
Solar circuit pump ON | 10 | °C | 0 to 30 | °C |
Solar circuit pump OFF | 2 | °C | 0 to 30 | °C |
Solar charging OFF | 70 | °C | 20 to 90 | °C |
|
|
|
|
|
6.4DHW heating in instantaneous heating system (Anl 6)
The controller regulates the DHW outlet temperature of the heat exchanger according to the ad- justed DHW temperature.
The circulation pump works according to the time schedule. We strongly recommend to operate the circulation pump during
To keep temperature peaks caused by load changes as small as possible, it is absolutely neces- sary that a temperature sensor with short response times (e.g. Type
Note!
The control parameter setting has great influence on the control accuracy in the case of DHW heating in instantaneous heating systems.
Parameter | WE | Range of values |
DHW temperature | 55 °C | 20 to 90 °C |
EB 5476 EN 53