Appendix
12 Appendix
12.1 Function block list
FB | Function | WE | Anl | Comments | |
0 | Optimization | OFF |
| FB0 = ON: Optimization active; when FB0 = ON also FB13 = | |
|
|
|
| ON |
|
1 | Adaptation | OFF |
| FB1 = ON: Adaptation active; when FB1 = ON also FB13 = ON | |
2 | Flash adaptation | OFF |
| FB2 = ON: Flash adaptation active; when FB2 = ON also | |
|
|
|
| FB13 = ON | |
3 | Summer mode | OFF |
| FB3 = ON: Summer mode active | |
|
|
|
| Function block parameters: | |
|
|
|
| Start summer mode / 01.01 to 31.12 (01.06) | |
|
|
|
| End summer mode / 01.01 to 31.12 (30.09) | |
|
|
|
| Outdoor temperature limit / 0 to 30 °C (18 °C) | |
4 | Delayed outdoor | OFF |
| FB4 = ON: Temperature adaptation active | |
| temperature |
|
| Ab: | Active when outdoor temperature drops |
| adaptation |
|
| AufAb: Active when outdoor temperature increases or drops | |
|
|
|
| Function block parameter: | |
|
|
|
| Delay / 0.2 to 6 °C/h (3 °C/h) | |
5 | Automatic summer | ON |
| FB5 = ON: Changeover active | |
| time/winter time |
|
|
|
|
| changeover |
|
|
|
|
6 | Public | OFF | 2 | FB6 = ON: Public holiday and vacation data entered also | |
| holidays/vacation |
| to | applies to DHW heating | |
| data for DHW |
| 11 |
|
|
7 | Thermal | OFF | 2, 3, | FB7 = ON: Thermal disinfection active; when FB7 = ON also FB14 | |
| disinfection |
| 4, 5, | = ON |
|
|
|
| 7, 8, | Function block parameter: | |
|
|
| 9,11 | Day of week / 1 to 7 (Mon to Sun), | |
8 | Priority for DHW | OFF | 4, 5, | FB8 = ON: Priority active | |
| circuit |
| 6, 7, | Ab: | Priority through |
|
|
| 8, | In: | Priority through reverse control |
|
|
| 11 | Function block parameter: | |
|
|
|
| Activate priority in case of deviation / 2 to 10 min (10 min) |
EB 5476 EN 81