12 Appendix

Appendix

12 Appendix

12.1 Function block list

FB

Function

WE

Anl

Comments

0

Optimization

OFF

 

FB0 = ON: Optimization active; when FB0 = ON also FB13 =

 

 

 

 

ON

 

1

Adaptation

OFF

 

FB1 = ON: Adaptation active; when FB1 = ON also FB13 = ON

2

Flash adaptation

OFF

 

FB2 = ON: Flash adaptation active; when FB2 = ON also

 

 

 

 

FB13 = ON

3

Summer mode

OFF

 

FB3 = ON: Summer mode active

 

 

 

 

Function block parameters:

 

 

 

 

Start summer mode / 01.01 to 31.12 (01.06)

 

 

 

 

End summer mode / 01.01 to 31.12 (30.09)

 

 

 

 

Outdoor temperature limit / 0 to 30 °C (18 °C)

4

Delayed outdoor

OFF

 

FB4 = ON: Temperature adaptation active

 

temperature

 

 

Ab:

Active when outdoor temperature drops

 

adaptation

 

 

AufAb: Active when outdoor temperature increases or drops

 

 

 

 

Function block parameter:

 

 

 

 

Delay / 0.2 to 6 °C/h (3 °C/h)

5

Automatic summer

ON

 

FB5 = ON: Changeover active

 

time/winter time

 

 

 

 

 

changeover

 

 

 

 

6

Public

OFF

2

FB6 = ON: Public holiday and vacation data entered also

 

holidays/vacation

 

to

applies to DHW heating

 

data for DHW

 

11

 

 

7

Thermal

OFF

2, 3,

FB7 = ON: Thermal disinfection active; when FB7 = ON also FB14

 

disinfection

 

4, 5,

= ON

 

 

 

 

7, 8,

Function block parameter:

 

 

 

9,11

Day of week / 1 to 7 (Mon to Sun), 1–7 (3)

8

Priority for DHW

OFF

4, 5,

FB8 = ON: Priority active

 

circuit

 

6, 7,

Ab:

Priority through set-back operation

 

 

 

8,

In:

Priority through reverse control

 

 

 

11

Function block parameter:

 

 

 

 

Activate priority in case of deviation / 2 to 10 min (10 min)

EB 5476 EN 81

Page 81
Image 81