4 | Sequence Of Operation |
|
|
4-1 Staging
1.The system uses a PID control algorithm to regulate the chilled water temperature. As the required control effort increases or decreases, the system compressors are turned on or off to keep the temperature at the specified
2.Compressor
4-2 Alarms
If a fault occurs, that compressor or circuit is deactivated. The load will automatically shift to any other compressors that are currently
4-3 Lead-Lag Compressors
The system automatically rotates the compressor order to generate a Lead/Lag rotation. Any time a compressor is faulted or manually taken
Once the fault is cleared or manually put
4-4 Lead-Lag Pumps
The system automatically rotates the pump order to generate a Lead/Lag rotation. Any time a pump is faulted or manually taken