SterlingTEK A0551797 manual Allow time to cool and reset

Models: A0551797

1 86
Download 86 pages 22.68 Kb
Page 78
Image 78

Problem

Possible Cause

Solution

 

 

Allow time to cool and reset.

 

 

Check for high/low voltage.

 

 

Voltage must be within plus

 

Compressor internal overload

or minus ten percent (±10%)

 

of nameplate rating.

 

open.

 

Check for poor compressor

 

 

 

 

electrical connections.

 

 

Check compressor rotation

 

 

on scroll compressors.

 

Compressor contactor

Repair or replace.

 

holding coil open.

Pump runs,

 

Defective fan motor.

Repair or replace.

compressor does not

Fan motor out on overload.

Reset and test.

(cont’d).

 

 

Defective freezestat.

Replace.

 

Refrigerant low.

Check the refrigerant charge.

 

Defective fan cycling control.

Replace.

 

 

Sight glass should be clear

 

Low refrigerant pressure

while comperssor runs. Call

 

switch contact open.

for service if bubbling or

 

 

foaming.

 

Defective pump motor

 

 

interlock to compressor

Repair or replace.

 

control circuit.

 

 

Broken wire in the

Locate and repair.

 

compressor control circuit.

 

 

 

Freezestat control setting is

Lower set point to 10°F (6ºC)

 

below the leaving water

Pump runs, compressor

too high.

temperature you want with at

 

least 15 degrees differential.

cycles at short intervals.

 

Check refrigeration charge;

 

Refrigerant is too low.

check refrigerant sight glass

 

for bubbles or a level in the

 

 

 

 

glass.

 

Improper water/glycol

Be sure the antifreeze

 

mixture protection is right for

Leaving water temperature is

mixture.

the process.

 

not at set point.

Defective freezestat control.

Replace.

 

Refrigerant charge is low.

Call service to find and repair

 

the leak. Add refrigerant.

 

 

 

 

Check for partially closed

Pump pressure is too high.

Restricted water flow.

valves etc. Be sure all lines

 

 

are properly sized.

Page 78 of 86

SSC Series Central Chilling Stations

Page 78
Image 78
SterlingTEK A0551797 manual Allow time to cool and reset