SterlingTEK A0551797 manual 10Troubleshooting, Problem Possible Cause Solution

Models: A0551797

1 86
Download 86 pages 22.68 Kb
Page 77
Image 77

10Troubleshooting

Problem

Possible Cause

Solution

 

No power.

Check main disconnect,

 

fuses, wiring, and power lead

 

 

to unit.

 

Wrong voltage supplied to

Voltage must be within plus

 

or minus ten percent (±10%)

 

unit.

 

of nameplate rating.

 

 

 

Defective On/Off switch.

Replace switch.

 

 

Replace fuse, check

 

 

transformer, check wiring for

 

Control circuit fuse blown.

loose wires, check for shorted

 

coils on contactors and

 

 

Unit does not run.

 

solenoids, check crankcase

 

 

heater.

 

Defective control transformer.

Replace.

 

Flow switch circuit is open.

Check pump for proper

 

rotation.

 

 

 

Pump motor off on overload.

Reset and test motor.

 

 

Check that the chiller pump is

 

Unit is off on flow switch or

running.

 

Check that all valves are

 

pressure switch.

open.

 

 

Check for defective flow

 

 

switch or pressure switch.

 

Freeze control set higher than

Lower freeze control setting

 

to 10°F (6ºC) below the

 

temperature of liquid in

 

leaving temperature you

 

system.

 

want.

 

 

 

 

Air cooled units: Check and

 

 

clean air filters. Check

 

 

condenser fans for proper

Pump runs,

 

rotation. Check for dirty

 

condenser. Check for

compressor does not.

High pressure refrigerant

condenser air obstruction.

 

Check for tripped motor

 

cutout switch contacts open.

overload, blown fuses, or bad

 

 

condenser fan motor.

 

 

Water cooled units: Check for

 

 

water valves turned on.

 

 

Check for dirty condenser.

 

 

Check water flow through

 

 

condenser.

SSC Series Central Chilling Stations

Page 77 of 86

Page 77
Image 77
SterlingTEK A0551797 manual 10Troubleshooting, Problem Possible Cause Solution