SterlingTEK A0551797 manual Operating Chiller Pumps, Pump Enables Screen

Models: A0551797

1 86
Download 86 pages 22.68 Kb
Page 51
Image 51

Operating Chiller Pumps

To turn on and off the pumps, start from the Main Menu, then:

nPress the or buttons to highlight either

CONFIGURATION MENU”.

nPress

nHighlight “PUMP ENABLES

nPress

nHighlight the pump you want to operate.

The Pump Enables Screen appears

Pump Enables Screen

Any pump that is disabled to the OFF-LINE position will not be called to operate. Simply toggle the F1 key on the enable/disable screen to toggle the state of the pump from the ON-LINE to OFF- LINE state.

Setting Pump Lead/Lag Times and Activating Pump Lead/Lag Operation

While in the Configuration Menu, the pump lead/lag screen allows the customer to enable or disable the Lead/Lag rotation of compressors. While viewing the screen for the applicable rotation, pressing F1 will toggle the rotation function On or Off. Pressing the F2 button will present an entry screen which will allow the entry of a rotation interval. Acceptable range is 50-200 hours.

SSC Series Central Chilling Stations

Page 51 of 86

Page 51
Image 51
SterlingTEK A0551797 manual Operating Chiller Pumps, Pump Enables Screen