SSC Series condensing pressure with 95ºF (35ºC) condenser air

R-22 = 260 psi (1,793 kPa/17.93 bars)

Note: Due to the variables involved in remote air-cooled condenser installations, no set or standard piping procedure exists. Each installation must be designed and installed by qualified persons. Follow the instructions supplied with the condenser.

3-11 Checking Motor Direction

Compressor

Note:

Never switch contactor leads or motor leads for reversing rotation.

Do not use contactor or motor leads for phase matching.

Compressor noise from reverse rotation is noticeable. Do not run in this mode for more than ten (10) seconds. The compressor shuts off if run longer in this mode.

Reverse rotation can cause suction and discharge pressures to be approximately equal; amp draws will be lower than normal.

If you discover that compressor rotation is reversed, correct it by switching any two main power leads into the disconnect switch or distribution block on the unit.

Water Pump

A positive pressure of 20 to 30 psi (137.9 to 206.8 kPa/1.38 to 2.07 bars) on the TO PROCESS line indicates correct pump rotation.

Condenser Fan

On SSC Series remote air-cooled units, air should draw through the condenser and discharge up from the condenser.

Changing fan rotation direction

Disconnect and lock out power at the fused disconnect.

If all fans are going backwards, reverse any two main power leads.

If only some of the fans are going backwards, switch any two of their respective motor leads.