SterlingTEK A0551797 manual SSC Series Central Chilling Stations

Models: A0551797

1 86
Download 86 pages 22.68 Kb
Page 20
Image 20

!DANGER

Improper electrical connections can damage the unit and cause serious operator injury or death!

Bring properly sized power leads and ground from a fused disconnect (installed by your electrician) to the unit. Provide external overcurrent protection to the unit, using circuit breakers or fuses. If you use fuses, make sure that they are dual-element time- delay fuses, sized according to your electrical code. Make sure that all electrical connections are tight.

Important!

1.Electrical connections must comply with all applicable electrical codes.

2.The chiller must be grounded in accordance with NEC Article 250.

3.Voltage must be within plus or minus ten percent (±10%) of the nameplate rating.

4.Make sure your installer provides external protection.

Check the electrical wiring schematic

provided in your Customer Information packet

for additional information.

Page 20 of 86

SSC Series Central Chilling Stations

Page 20
Image 20
SterlingTEK A0551797 manual SSC Series Central Chilling Stations