7-5 Viewing and Operating Chiller Pumps

If your chiller system was configured to operate the pump(s) of the chilled water pump tank the user may view the status of the process and recirculation pumps.

Viewing Chiller Pump Status

To view the status of the pumps, start from the Main Menu, then:

nPress the or buttons to highlight either “PROC PUMP STATUS”or “RECIRC PUMP STATUS”.

nPress

The Pump Status Screen appears

Pump Status Screen

Only pumps that are included in the system will be shown on this screen. Pumps will display one of the following states:

1.OFFLINE – This indicates that the pump has been turned off in the pump enable/disable screen. The pump will not be called to operate until it has been re-enabled.

2.READY – Indicates that the pump is enabled and ready to run. However, the current number of pumps specified to run does not require this pump to operate.

3.RUNNING – Pump is currently running.

4.FAULT – A safety on the pump indicates a fault condition and the pump has been deactivated. Once the problem is remedied, the pump will return to a READY state unless it is put in the OFFLINE state.

Page 50 of 86

SSC Series Central Chilling Stations

Page 50
Image 50
SterlingTEK A0551797 manual Viewing and Operating Chiller Pumps, Viewing Chiller Pump Status, Pump Status Screen