SterlingTEK A0551797 manual Volume, Freezing Protection Curve

Models: A0551797

1 86
Download 86 pages 22.68 Kb
Page 29
Image 29

If you want lower chilled water temperatures, you’ll need to mix process water with industrial- (not automotive) grade ethylene or propylene glycol with rust inhibitor to provide protection down to 20°F (12ºC) below the operating temperature you want. Figure 3 below shows the proper mixtures needed to provide protection to 20°F (12ºC) below the operating temperature you want. You can then reset the freezestat cutout temperature to a temperature 10°F (6ºC) below the operating temperature you selected.

Caution!

Make sure all freezestat adjustments are performed

by a qualified refrigeration service technician.

The Sterling product warranty does not cover system freeze-up!

Figure 3

Freezing Protection Curve

Ethylene glycol required for evaporator freeze protection

 

60

 

 

 

 

 

 

 

 

50

 

 

 

 

 

 

 

Ethylene

40

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

glycol

30

 

 

 

 

 

 

 

percent by

 

 

 

 

 

 

 

 

volume

20

 

 

 

 

 

 

 

 

10

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

-50ºF -40ºF -30ºF -20ºF -10ºF

0ºF

10ºF

20ºF

30ºF

40ºF

50ºF

60ºF

 

-46ºC -40ºC -34ºC -29ºC -23ºC -18ºC -12ºC

-7ºC

-1ºC

4ºC

10ºC

16ºC

Chilled water operating temperature ºF / ºC

SSC Series Central Chilling Stations

Page 29 of 86

Page 29
Image 29