High Pressure Cutout

 

 

 

 

 

This electro-mechanical safety feature opens the control circuit if

 

the system condensing pressure exceeds a safe level.

 

 

 

 

 

 

 

 

High pressure cutout setting

 

 

 

 

Model

 

psi

kPa

 

bars

SSC Series water-cooled chilling stations

 

290 psi

2,000 kPa

 

20 bars

SSC Series remote air-cooled chilling stations

 

375 psi

2,586 kPa

 

26 bars

Important!

The high pressure cutout is a manual reset control,

so you should reset it once.

If the problem persists, call a refrigeration service technician

to analyze the problem and to reset the control.

4-9 Low Pressure Cutout

This encapsulated switch safety feature prevents the compressor suction pressure from dropping below a pre-set point. It is factory set to open the control circuit when pressure drops below a safe level. The chiller will need to be restarted when the suction pressure reaches above 65 psi (448.2 kPa/4.5 bars).

 

Opens control circuit @

Resets control circuit @

Model

psi

kPa

bars

psi

kPa

bars

SSC Series water-cooled chilling stations

15 psi

103.4 kPa

1.0 bars

30 psi

206.9 kPa

2.1 bars

SSC Series remote air-cooled chilling

15 psi

103.4 kPa

1.0 bars

30 psi

206.9 kPa

2.1 bars

stations

 

 

 

 

 

 

4-10 Flow Switch

The flow switch shuts down the chiller if the evaporator water flow falls below a safe operating gallons-per-minute (liters-per-minute) flow rate.