9-3 Evaporator Maintenance

The evaporator(s) may be accessed for back-flushing by removal of the 2” plug (approx. 51 mm) in the return control nipple and the flow switch in the supply control nipple. If the suggested piping recommendations have been followed, one circuit of a multiple circuit chiller may be back-flushed without shutting down the entire system. Check Y-strainer for any clogging.

9-4 Pump Motor Seal

Pump seals require water for lubrication, so the pump(s) must never be run dry. Always fill the tank before attempting to operate the pump(s). Seal failures usually follow a period of dry operation of the pump.

9-5 Makeup Valve

Periodically inspect the water makeup valve assembly for proper operation. If the valve no longer shuts off completely or reliably, replace it. The plastic ball float should be buoyant for proper operation.

9-6 Recommended Pump Tank Spare Parts

Part no.

Part description

Quantity

A0550190

Pressure gauge

1 per pump

A0102396

Float valve, 1” (approx. 25 mm)

1 per tank

A0069538

Plastic ball float, 6” (approx. 152 mm)

1 per tank

A0102394

Float rod, 10” (25 cm)

1 per tank

- Call Sterling

Pump seal and casing gasket

1 per pump

Parts -

 

 

Check your Customer Information Packet for a complete list of spare parts and part numbers for your SSC Series chilling station.