Sun Microsystems Sun Fire V100 manual Boolean Causes LOM to disable its

Models: Sun Fire V100

1 146
Download 146 pages 47.17 Kb
Page 140
Image 140

TABLE B-1LOM Configuration File Parameters (Continued)

Field

Format

Default

Effect

 

 

 

 

disable_wdog_on_break=

Boolean

1

Causes LOM to disable its

 

0=FALSE

 

watchdog if it detects a break

 

1=TRUE

 

signal on the Serial A/LOM

 

 

 

port.

disable_wdog_on_panic=

Boolean

1

Causes LOM to try to disable its

 

0=FALSE

 

watchdog after a system

 

1=TRUE

 

“panic”.

faulty_voltage_shutdown=

Boolean

1

Causes LOM to attempt first to

 

0=FALSE

 

shut down the system and, if

 

1=TRUE

 

that fails, to power off the

 

 

 

system in the event of a

 

 

 

problem with the supply rails.

enclosure_warning_temp=

oC

67

Specifies the temperature at

 

 

 

which LOM generates an

 

 

 

overtemperature event.

over_temperature_shutdown=

Boolean

1

Causes LOM to attempt to shut

 

0=FALSE

 

down the system, or to power it

 

1=TRUE

 

off, if the enclosure temperature

 

 

 

exceeds the level specified for

 

 

 

the enclosure_shutdown_temp

 

 

 

parameter.

enclosure_shutdown_temp=

oC

72

Specifies the enclosure

 

 

 

temperature above which LOM

 

 

 

attempts to shut the system

 

 

 

down or, if this fails, to power

 

 

 

the system off. (LOM will

 

 

 

attempt to do either of these if

 

 

 

over_temperature_shutdown is

 

 

 

set to 1.)

serial_security=

Boolean

1

Enables and disables the user

 

0=FALSE

 

security facilities even if user

 

1=TRUE

 

security has been configured.

 

 

 

You can use this parameter to

 

 

 

set up users again if your users

have forgotten their passwords. Cannot be turned on if no users are configured in the LOM.

122 Sun Fire V100 Server User’s Guide • December 2001

Page 140
Image 140
Sun Microsystems Sun Fire V100 manual Boolean Causes LOM to disable its