7.2.25 Communications Port Options

The 9060Z transmitter has a serial communications port available at terminals 18 to 22. The default protocol is for RS‐232 running at 19,200 baud rate with 8 bits, Even parity and 1 stop bit.

 

 

 

Function

 

 

Options

 

 

 

 

60

 

 

Serial Interface

 

 

RS‐232 or RS‐485 (Use RS‐485 for MODBUS)

 

 

 

61

 

 

Serial Baud Rate

 

9600, 19200, 38400, 57600 (RS‐232 up to 19200 only)

62

 

 

Serial Parity

 

 

Even, Odd or No Parity

63

 

 

MODBUS

 

Set the MODBUS address for this device between 1 and 246.

 

Address

 

0 is to disable the MODBUS

7.2.26 Alarm Log Clearing

Every alarm that is instigated internally in the transmitter or as a process level is recorded in the alarm log with the activation time, accepted time and the cleared time. The last 4000 events will be recorded and then the oldest alarms will be dropped off as new ones occur. If you would like to delete the log recording select CLEAR in SETUP step 64 by using the OPTION keys and press the ENTER key. The message “Alarm Log Cleared” will be displayed.