7.2.25CommunicationsPortOptions
The9060Ztransmitterhasaserialcommunicationsportavailableatterminals18to22.Thedefault
protocolisforRS232runningat19,200baudratewith8bits,Evenparityand1stopbit.
Function Options
60SerialInterface RS232orRS485(UseRS485forMODBUS)
61SerialBaudRate 9600,19200,38400,57600(RS232upto19200only)
62 SerialParity Even,OddorNoParity
63 MODBUS
Address
SettheMODBUSaddressforthisdevicebetween1and246.
0istodisabletheMODBUS
7.2.26AlarmLogClearing
Everyalarmthatisinstigatedinternallyinthetransmitterorasaprocesslevelisrecordedinthealarm
logwiththeactivationtime,acceptedtimeandtheclearedtime.Thelast4000eventswillbe
recordedandthentheoldestalarmswillbedroppedoffasnewonesoccur.Ifyouwouldliketodelete
thelogrecordingselectCLEARinSETUPstep64byusingtheOPTIONkeysandpresstheENTERkey.
Themessage“AlarmLogCleared”willbedisplayed.
