5.1Wiring/Connection
WARNING
Perform wiring and connections with correct polarity.
Be careful when connecting the UPS to the battery system. A wrong connection may cause damage to the UPS, battery, or charger.
Connect ONLY one (1) ground wire to the earth ground terminal.
A missing ground wire may cause an electrical shock hazard.
Connecting to more than one ground may cause a ground loop.
See Chapter 11 - UPS Wiring
DO NOT force, bend, or pull wires.
DO NOT damage wire insulation.
DO NOT place heavy objects on top of UPS.
Observe the above precautions when making wire connections or handling the wires. Failing to observe these precautions may damage the insulation of the wires or may cause a fire or an electric shock hazard.
ATTENTION
Follow the torque criteria for tightening screws.
Loose connections may cause fire due to heating.
See Chapter 11 - UPS Wiring
G8000 Series with Isolated Output Installation and Operation Manual | 13 |