Toshiba G8000 operation manual Block Number Cable Size Tightening Torque 100 KVA 150 KVA

Models: G8000

1 74
Download 74 pages 20.32 Kb
Page 39
Image 39

table 11.1 Recommended crimp type compression lugs

Wire Size

Wire

Recommendation

Crimp tool Required

 

Strand

 

 

Burndy type Y35 or Y46

 

Class

Vendor

Cat. No.

Color Key

Die Index

1/0

B

Burndy

YA25

Pink

12 / 348

 

I

Ilsco

CRA-1/OL

Pink

12 / 348

 

B

Burndy

YA25-LB

Black

13

2/0

B

Burndy

YA26

Black

13

 

I

Ilsco

CRA-2/OL

Black

13

 

B

Burndy

YA27-LB

Orange

14 / 101

3/0

B

Burndy

YA-27

Orange

14 / 101

 

I

Ilsco

CRB-3/OL

Orange

14 / 101

 

B

Burndy

YA28-LB

Purple

15

4/0

B

Burndy

YA28

Purple

15

 

I

Ilsco

CRB-4/OL

Purple

15

 

B

Burndy

YA29-LB

Yellow

16

300 MCM

B

Burndy

YA30

White

17 / 298

 

I

Ilsco

CRA-30OL

White

17 / 298

 

B

Burndy

YA32-LB

Red

18 / 324

table 11.2 recommended cable size and tightening torque for 100 KVA and 150 KVA UPS

Block Number

Cable Size

Tightening Torque

 

100 KVA

150 KVA

 

1

AWG 2/0 or larger

AWG 4/0 or larger

275 in-lbs. (3.2 kg-m)

2

AWG 2/0 or larger

AWG 4/0 or larger

275 in-lbs. (3.2 kg-m)

3

AWG 2/0 or larger

AWG 4/0 or larger

275 in-lbs. (3.2 kg-m)

4

AWG 2/0 or larger

AWG 4/0 or larger

275 in-lbs. (3.2 kg-m)

5

AWG 2/0 or larger

AWG 4/0 or larger

275 in-lbs. (3.2 kg-m)

6

AWG 2/0 or larger

AWG 4/0 or larger

275 in-lbs. (3.2 kg-m)

7

Two AWG 2/0 or larger

Two AWG 4/0 or larger

275 in-lbs. (3.2 kg-m)

8

Two AWG 2/0 or larger

Two AWG 4/0 or larger

275 in-lbs. (3.2 kg-m)

9

Two AWG 2/0 or larger

Two AWG 4/0 or larger

275 in-lbs. (3.2 kg-m)

10

Two AWG 2/0 or larger

Two AWG 4/0 or larger

275 in-lbs. (3.2 kg-m)

*11

Two AWG 3/0 or larger

Two 300 MCM or larger

275 in-lbs. (3.2 kg-m)

*12

Two AWG 3/0 or larger

Two 300 MCM or larger

275 in-lbs. (3.2 kg-m)

13

AWG 2/0 or larger

AWG 4/0 or larger

275 in-lbs. (3.2 kg-m)

NOTE: Maximum cable size is 350 MCM

*One battery string (SEE NOTE, PAGE 36, if using multiple battery strings

G8000 Series with Isolated Output Installation and Operation Manual

31

Page 39
Image 39