3)The UPS should not be used with a load that has a rated input that is greater than the rated output of the UPS.

4)If using the UPS to provide power to motors that require high starting current or with motors that require a long starting time, call Toshiba support for guidance in over sizing the UPS for lock rotor current.

5)DO NOT insert metal objects or combustible materials in the ventilation slots of the UPS.

6)DO NOT place, hang, or paste any objects on the exterior surfaces of the UPS.

7)The capacitors of the UPS maintain a residual charge for a while after turning off the UPS. The required discharge time for each UPS is provided via a cabinet label. Wait for at least the minimum time indicated on the label and ensure that the front panel LED’s have gone out before removing the front panel of the UPS once the UPS power has been turned off.

8)DO NOT attempt to disassemble, modify, or repair the UPS. Call your Toshiba sales representative for repair information.

9)Turn the power on only after installing ALL of the covers.

10)DO NOT remove any covers of the UPS when power is on.

11)If the UPS should emit smoke or an unusual odor or sound, turn all power sources off immediately.

12)Warning signs should be placed on or near the load as a notification that the load is being powered by the UPS.

13)Additional warnings and notifications shall be posted at the equipment installation location as deemed required by Qualified Personnel.

WARNING

While operating in the inverter mode, placing the input breaker in the “OFF” position will switch the UPS to the battery backup mode.

The output of the UPS will continue uninterrupted to the load. The unit must be in the bypass mode at the time that the breaker is placed in the “OFF” position for the UPS to shutdown power to the load.

caution

After an Emergency Power Off (EPO), DO NOT reset the breaker until the UPS internal circuits have been fully discharged.

The UPS could be damaged if the unit is not fully discharged before the breaker is reset.

G8000 Series with Isolated Output Installation and Operation Manual