12.3Electrical Specification
warning
DO NOT open the front cover.
Electric shock, burns or other personal injuries may occur if unqualified personnel open the front cover.
AC Input Rated Capacity | 100 kVA (80 kW) | 150 kVA (120 kW) |
Input Voltage | 480 V ( +10% – | |
| ||
Input Frequency | 60 Hz ±5% | |
Input Power Factor | 1.00 – 0.95 Lagging ( at 100% Load ) | |
Current Harmonic Distortion | 5% Maximum ( at 100% Load ) | |
Input Capacity Required | 107 kVA | 154 kVA |
Circuit Breaker Rating At 480 V Input | 200 A | 250 A |
|
|
|
| DC Input Rated Capacity |
| 100 kVA (80 kW) |
| 150 kVA (120 kW) |
| |
| Voltage Window |
| 288 – 414 V |
| |||
| Recharge Voltage Regulation |
| ± 1.5% |
| |||
|
|
|
|
|
| ||
AC Output Rated Capacity |
| 100 kVA (80 kW) |
|
| 150 kVA (120 kW) | ||
Output Voltage |
| 208/120 V ± 1%, | |||||
Output Power Factor |
| 0.8 Lagging | |||||
Voltage Distortion | 3% with 100% Linear Load / 5% with | ||||||
|
|
|
| Load | |||
Transient Voltage Regulation |
|
| < ± 2% |
| |||
Transient Settling Time |
| < 50 msec | |||||
Crest Factor |
|
| < 2.0 |
| |||
Output Frequency |
| 60 Hz ± 0.01% ( at | |||||
Synchronous Window To Utility Line |
| 59 Hz – 61 Hz | |||||
Frequency Slew Rate |
| 1 Hz/Sec | |||||
Over Load Rating |
G8000 Series with Isolated Output Installation and Operation Manual | 39 |