Toshiba G8000 operation manual UPS Specifications, General Specification, Mechanical Specification

Models: G8000

1 74
Download 74 pages 20.32 Kb
Page 45
Image 45

12 UPS Specifications

12.1General Specification

Terms

Specification

Remarks

Conforming Standard

UL1778-2001

UL, cUL, IEC

Ambient Temperature

32 – 104 °F (0 – 40 °C)

 

Relative Humidity

30% – 90%

Non-condensing

Altitude

< 3,280 ft (< 1,000 m)

Contact Toshiba Technical Support for

 

instalation above 3280 ft. (1000 m)

 

 

Audible Noise

68dB(150 kVA)

1m (39”) away from front

Insulation Resistance

3 MΩ

With 500 V-Megger

 

AC 2 kV – 1 min.

Main Circuit

Insulation Breakdown

AC 1.5 kV – 1 min.

External Interface

 

AC 500 V – 1 min.

Control Circuit

12.2Mechanical Specification

Rated Capacity

100kVA

Cabinet

 

Protection

IEC298 IP20*

Conformity

 

Exterior Paint

Sherwin Williams, HHT2-7055, 079 Beige Texture

 

FRONT: 1/16 in. (1.6mm)

Panel Thickness

BACK/SIDE/TOP: 3/64 in. (1.2mm)

 

BOTTOM: 1/8 in. (3.2mm)

Input/Output

BOTTOM

Cabling Entrance

 

Ground/Control

BOTTOM

Wiring Entrance

 

Outline

W: 36.8 in. (935 mm)

D: 31.8 in. (808 mm)

Dimension

H: 79.2 in. (2,012 mm)

 

Unit Weight

2006 lb (1000 kg))

Shipping Weight

2096 lb (1041.4 kg)

Floor Loading

2446 lbs/ft2

Per Footprint

(13,126 kg/m2)

 

FRONT: 43 7/16 in. (1,100 mm)

Clearance

BACK/SIDE: 0 in. (0 mm)

 

TOP: 15 3/4 in. (400 mm)

Heat Rejection

27,620 BTU/h

(6,960 kcal/h)

 

*IP20: Foreign objects that are 12mm (15/32”) or larger are prevented from entering the enclosure of the UPS.