Toshiba G8000 operation manual Grounding Wire, Be sure to ground the UPS as specified

Models: G8000

1 74
Download 74 pages 20.32 Kb
Page 41
Image 41

11.3Grounding Wire

WARNING

Be sure to ground the UPS as specified.

Using the UPS without a proper ground will deteriorate the insulation, cause leakage of currents and electric shock.The resistance to ground should be less than or equal to 10 ohms.

The 100/150 kVA earth grounding bus is located inside, at the bottom-front of the unit. The 150 kVA earth grounding buss is accessable through either the bottom or top knockout panel.

Use a 2 AWG (or 38 mm2) or larger cable for the grounding wire. Run the grounding wire through the opening at the bottom, or alternately through the top if a 150 kVA unit.

The ground wire must have a crimp terminal with a 1/2” (12 mm) diameter bolt hole. The ground bus has a 33/64” (13 mm) bolt hole. The crimp terminal and ground bus should be connected together using a 7/16” (10 mm) diameter bolt.

100 kVA

150 kVA

Facility earth ground. Alternate ground wire routing through top knockout plate.

Ground bus

10 mm or

 

7/16” Bolt

 

12 mm or 1/2”

 

Terminal

2 AWG (38 mm2)

 

ground wire

Feed-through opening

To facility

earth ground

Ground bus

10 mm or

 

7/16” Bolt

 

12 mm or 1/2”

 

Terminal

2 AWG (38 mm)

 

ground wire

Feed-through opening

To facility

earth ground

Note: Use either the top or the bottom access for the ground wire to connect to the ground buss, but use only one ground wire.

Figure 11.7 - EARTH GROUND WIre

G8000 Series with Isolated Output Installation and Operation Manual

33

Page 41
Image 41
Toshiba G8000 operation manual Grounding Wire, Be sure to ground the UPS as specified