Cable knockout plates are provided at the bottom of the 100 kVA UPS, and at the bottom and top of the 150 kVA UPS. The recommended hole locations are illustrated in Figure 11.4 - 11.6

The five (5) holes must be punched during installation. The dashed rectangle indicates the UPS opening behind the knockout plates.

plate #1

plate #2

0.8”

3” Dia.

 

 

2” Dia.

 

0.8”

 

 

 

 

 

 

 

 

AC INPUT

BYPASS

AC OUTPUT BATTERY

CONTROL

 

 

 

WIRES

FIGURE 11.4 - Bottom CABLE KNOCKOUT PLATES - 100 kVA)

plate #1

 

plate #2

plate #3

0.8”

 

4” Dia.

 

 

 

 

 

2” Dia.

 

4” Dia.

 

 

 

 

 

 

0.4”

 

 

 

 

 

 

 

 

 

 

 

 

 

AC INPUT

 

BYPASS

AC OUTPUT

BATTERY

CONTROL

FIGURE 11.5 - Bottom CABLE KNOCKOUT PLATES - 150 kVA

 

WIRES

 

 

 

FIGURE 11.6 - Top CABLE KNOCKOUT PLATE - 150 kVA

11.2External Breakers

The G8000 UPS units are not equipped with circuit breakers. Qualified personnel should provide the external breakers for the AC input/output, bypass input and DC input.

See Figure 11.1 – External Wiring Diagram, for the circuit position of the breakers.

Table 11.3 shows the G8000 UPS minimum external breaker rating for each capacity. The bypass input and the AC output require 3-pole breakers.

 

 

Table 11.3 EXTERNAL BREAKER RATING

 

 

Capacity

AC Input / Bypass Input / AC Output

 

DC Input

 

Minimum Breaker Rating

 

Minimum Breaker Rating

 

 

 

 

100 kVA

480V - 200A / 480V - 200A / 208V - 350A

 

500 VDC – 400 A

 

150 kVA

480V - 250A / 480V - 250A / 208V - 600A

 

500 VDC – 600 A

 

 

 

 

 