Cable knockout plates are provided at the bottom of the 100 kVA UPS, and at the bottom and top of the 150 kVA UPS. The recommended hole locations are illustrated in Figure 11.4 - 11.6
The five (5) holes must be punched during installation. The dashed rectangle indicates the UPS opening behind the knockout plates.
plate #1 | plate #2 |
0.8”
3” Dia. |
|
| 2” Dia. | |
| 0.8” |
|
|
|
|
|
|
|
|
AC INPUT | BYPASS | AC OUTPUT BATTERY | CONTROL | |
|
|
| WIRES | |
FIGURE 11.4 - Bottom CABLE KNOCKOUT PLATES - 100 kVA) | ||||
plate #1 |
| plate #2 | plate #3 |
0.8”
| 4” Dia. |
|
|
|
|
| 2” Dia. |
| 4” Dia. |
|
|
|
|
| |
| 0.4” |
|
|
|
|
| |
|
|
|
|
|
|
|
|
AC INPUT |
| BYPASS | AC OUTPUT | BATTERY | CONTROL | ||
FIGURE 11.5 - Bottom CABLE KNOCKOUT PLATES - 150 kVA |
| WIRES | |||||
|
|
|
FIGURE 11.6 - Top CABLE KNOCKOUT PLATE - 150 kVA
11.2External Breakers
The G8000 UPS units are not equipped with circuit breakers. Qualified personnel should provide the external breakers for the AC input/output, bypass input and DC input.
See Figure 11.1 – External Wiring Diagram, for the circuit position of the breakers.
Table 11.3 shows the G8000 UPS minimum external breaker rating for each capacity. The bypass input and the AC output require
|
| Table 11.3 EXTERNAL BREAKER RATING |
| |
| Capacity | AC Input / Bypass Input / AC Output |
| DC Input |
| Minimum Breaker Rating |
| Minimum Breaker Rating | |
|
|
| ||
| 100 kVA | 480V - 200A / 480V - 200A / 208V - 350A |
| 500 VDC – 400 A |
| 150 kVA | 480V - 250A / 480V - 250A / 208V - 600A |
| 500 VDC – 600 A |
|
|
|
|
|