14.1Operation Types
The operation types are summarized below.
| TABLE 11.1 OPERATION TYPES |
Operation | Description |
Startup | Starting up and operating the UPS. |
Switch Power Supply | Switching power supply source between UPS and Bypass. |
Stop | Stop the inverter and chopper/charger. |
Complete Shutdown | Turn off the control power supply. Shut down the UPS completely. |
Float / Equalize Charge | Changing the battery recharge mode between float charge and |
| equalize charge. |
Protection Charge | Automatic recharge mode transition from protection charge to float |
| charge. |
EPO (Emergency Power Off) Opens up UPS input and output circuit breakers. Now power flows through the unit.
14.2Pre-operational Check
CAUTION
Perform the pre-operational check before operating the UPS.
Before operating the UPS:
1.Make sure all covers/panels are in place and secured.
2.Make sure the temperature in the UPS/Battery room is within specified limits.
3.Before starting the UPS, check the power source to make sure AC input power is on.
4.Make sure battery breaker’s auxiliary
G8000 Series with Isolated Output Installation and Operation Manual | 49 |