Xantrex Technology PV100S-480 installation manual 3 Environmental Specifications

Models: PV100S-480

1 90
Download 90 pages 29.08 Kb
Page 26
Image 26
Environmental Specifications

Introduction

Environmental Specifications

The following environmental specifications are the same for both models of the PV100S 100 kW Grid-Tied Photovoltaic Inverter.

Table 1-3Environmental Specifications

Specification

Value

 

 

Dimensions

 

Inverter and DC Interface

82 in H x 60 1/4 in W x 22 in D

 

(208 cm H x 153 cm W x 56 cm)

Transformer and AC Interface

44 in H x 50 in W x 34 in D

 

(112 cm H x 127 cm W x 86 cm D)

Overall System Footprint:

12 ft W x 6 ft L (approximate)

Layout Option A

 

(3.6 m x 1.8 m)

Layout Option B

9 ft W x 7 ft L (approximate)

 

(2.7 m W x 2.1 m L)

 

 

Weight

 

Inverter and DC Interface

1000 lbs (approximate)

Transformer and AC Interface

1400 lbs (approximate)

Overall Weight

2400 lbs (approximate)

 

 

Allowable Ambient Temperature

 

Operating

-20 °C to 50 °C Maximum

Storage

-40 °C to 50 °C Maximum

 

 

Relative Humidity

To 95%, Non-condensing

Elevation

Power Derated above 6600 ft

 

 

Clearance (ventilation and

In front of access doors: 36 in (91 cm)

serviceability)

In front of access panels: 36 in (91 cm)

 

 

Sides: 12 in (30 cm)

 

Back: 6 in (15 cm)

 

 

Maximum Distance between Main

15 ft (4.5 m)

Inverter Enclosure and AC

 

Interface/Transformer Enclosure

 

 

 

1–6

152315 Rev C

Page 26
Image 26
Xantrex Technology PV100S-480 installation manual 3 Environmental Specifications, In front of access doors 36 in 91 cm