Specifications
Install
A Schematics
Dimension
Wiring Requirements
To connect the main inverter to AC interface/transformer assembly
Operational Safety Procedures
System Status and Fault Reporting
A phase
Safety
Page 8
Image 8
vi
Page 7
Page 9
Page 8
Image 8
Page 7
Page 9
Contents
PV100S-208 PV100S-480
Planning and Installation Manual
PV100S 100 kW Grid-Tied Photovoltaic Inverter
Page
Planning and Installation Manual
PV100S 100 kW Grid-Tied Photovoltaic Inverter
About Xantrex
Trademarks
Notice of Copyright
Disclaimer
About This Manual
Purpose
Scope
Audience
Conventions Used
Abbreviations and Acronyms
Related Information
Page
Important Safety Instructions
SAVE THESE INSTRUCTIONS - DO NOT DISCARD
WARNING Shock Hazard
WARNING Lethal Voltage
General Safety Precautions
Personal Safety
Safety Equipment
Wiring Requirements
CAUTION Fire Hazard
WARNING Shock Hazard
Operational Safety Procedures
Lockout and Tag
To isolate the PV100S
De-Energize/Isolation Procedure
Interconnection Standards Compliance
Page
2 Planning
Contents
1 Introduction
3 Installation
A Schematics
4 Verification
Verification Procedure Summary
Tables
Page
Figures
Figure 3-18 AC Terminal Connections from the Utility- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -3-18 Figure 3-19 PV Array Cable Routing and Terminations - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -3-19 Figure 3-20 Telephone Cable Routing - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -3-21 Figure 3-21 RS232/FO Converter Kit Installation- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -3-23 Figure 3-22 Direct Connect Installation - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -3-24 Figure A-1 Electrical Diagram sample- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - A-3 Figure A-2 PV100S-480 Schematic for Main Power Distribution 152316 E1 - - - - - - - - - - - - - - A-4 Figure A-3 PV100S-480 Schematic for Control Power Distribution 152316 E2 - - - - - - - - - - - - - A-5 Figure A-4 PV100S-480 Schematic for Converter Control Unit 152316 E3- - - - - - - - - - - - - - - - A-6 Figure A-5 PV100S-208 Schematic Main Power Distribution 152376 C1 - - - - - - - - - - - - - - - - - A-7 Figure A-6 PV100S-208 Schematic for Control Power Distribution 152376 C2 - - - - - - - - - - - - - A-8 Figure A-7 PV100S-208 Schematic for Converter Control Unit 152376 C3- - - - - - - - - - - - - - - - A-9
1 Introduction
Description of the PV100S
Figure 1-1 Dimensions Not to scale
49 7/8 124.8 cm
60 ¼ 150.5 cm
59 ¼ 148 cm
System Specifications
Electrical Specifications
CAUTION Equipment Damage
Over Voltage, Under Voltage and Frequency Ranges
System Ground Requirements
System Neutral Requirements
Utility Side Isolation Transformer Requirements
CAUTION Equipment Damage
Environmental Specifications
Table 1-3 Environmental Specifications
In front of access doors 36 in 91 cm
In front of access panels 36 in 91 cm
Main Enclosure Door Interlock Switch
Operator Interface Controls
On/Off Switch
Figure 1-3 On/Off Switch
WARNING Shock Hazard
WARNING Shock Hazard
Communication Features
AC and DC Disconnect Switches
System Status and Fault Reporting
Data Logging
Communication Methods
Universal Front Panel Control Unit UFCU
PC Connection Methods
Figure 1-7 POTS Access
POTS Access
Wireless Access
Ethernet LAN Access
Direct Access
Figure 1-9 Ethernet LAN Access
Figure 1-10 Direct Access
2 Planning
Overview of PV100S Installation
WARNING Shock Hazard
Ventilation and Serviceability Requirements
PV Planning
Ground Requirements
System Neutral Requirements
Communication Requirements
Utility Side Isolation Transformer Requirements
Electrical Diagrams and Schematics
CAUTION Equipment Damage
WARNING Lethal Voltage
Model PV100S-480
Layout Options
Figure 2-1 PV100S Layout Option A
Minimum Dimension of Base Approximately 9 ft by 7 ft 2.7 m x 2.1 m
Figure 2-2 PV100S Layout Option B
Conduit Penetration
Figure 2-3 Conduit Entry Figure Reference
6 15 cm 2 5 cm 12 30 cm
6 15 cm
2 5 cm 6 15 cm
12 30 cm
Figure 2-8 Communications Enclosure Conduit Entry, Bottom Side
Figure 2-6 AC Interface Enclosure Conduit Entry, Left Side
Figure 2-7 DC Interface Enclosure, Bottom Side
Conductor and Conduit Sizing
CAUTION Equipment Damage
To calculate the proper conduit size
Step 1. Determine the required cable ampacity
Sense/Control Wires
Step 3. Size the cable
Step 4. Size the conduit
DLO 3/0 AWG Cable
Anchoring the PV100S
29 73.7 cm
5/8 1.5 cm x4
16 ¼ 40.6 cm
Figure 2-10 AC Interface/Transformer Anchor Bolt Pattern Not to Scale
17 ½73.7 cm 44 cm
63.5 cm ¾ 1.9 cm x6
Planning
3 Installation
WARNING Heavy Equipment
Equipment Required
Unloading
Moving the PV100S
Unpacking the PV100S
CAUTION Equipment Damage
To move the PV100S while it is still inside the shipping crates
Removing the Pallet and Moving the PV100S CAUTION Equipment Damage
Lift Here
To move the PV100S using a forklift
Lift Here
Mounting and Anchoring the Units
To mount and anchor the PV100S
Opening or Closing Access Doors
Figure 3-4 Inverter Enclosure Access Doors
Installation
To lock or unlock the front door on the main inverter
To Open Access Door
To Close Access Door
Figure 3-5 AC Interface Access Door
To Open Access Door
Figure 3-7 Transformer Access Panels
Figure 3-8 Inductor Access Panels
Installation
Transformer Access Panel
Conduit Installation
To install the conduits
Wiring - General
WARNING Shock Hazard
WARNING Lethal Voltage
CAUTION Equipment Damage
Overcurrent Protection
Conductor Termination
CAUTION Equipment Damage
See Figure 3-14 on page 3-15 for the location of these terminals
Wire Gauge and Torque Requirements
Grounding
Figure 3-11 Chassis Ground Bar TB1
System Neutral Requirements
Utility Side Isolation Transformer Requirements
Wiring - Specific
AC Connections
To connect the main inverter to AC interface/transformer assembly
CAUTION Equipment Damage
Figure 3-13 Tie-wraps on the AC Sense Harness
Transformer Enclosure
A phase
C phase
B phase
Figure 3-15 AC Terminal Connections in the Main Inverter Enclosure
To connect the utility service to AC Interface Enclosure
CAUTION Equipment Damage
S1-2T1 A Phase terminal
S1-6T3 C Phase terminal
S1-4T2 B Phase terminal TB6 Neutral Ground TB2
Figure 3-18 AC Terminal Connections from the Utility
PV Array Connections
Figure 3-19 PV Array Cable Routing and Terminations
PC Communications
PC Connection Methods
Establishing a POTS Connection
To connect a personal computer using the POTS Connection
Establishing Wireless Connection
Establishing an Ethernet LAN Connection
To connect a personal computer using the GSM Wireless modem
To connect a personal computer using the Ethernet LAN Connection
Direct Connection
If connecting the PC directly to the inverter
Figure 3-22 Direct Connect Installation
Installation
3-24
152315 Rev C
4 Verification
Verification Procedure Summary
WARNING Electrocution Hazard
Inspect the following items prior to completion of the installation
WARNING Shock Hazard
Visual Inspection of Mechanical Connections
Visual Inspection of Electrical Connections
To perform a visual inspection of the PV100S mechanical connections
To perform a visual inspection of the PV100S electrical connections
Visual Inspection, Isolation Transformer Wye/Wye
Corrective Action
To perform a visual inspection of the Isolation Transformer Wye/Wye
Perform after initial inspection if required
A Schematics
Appendix A contains useful schematics to aid with installation
152315 Rev C
This page intentionally left blank
Schematics
Figure A-1 Electrical Diagram sample
Schematics
Appendix A
152315 Rev C
Figure A-2 PV100S-480 Schematic for Main Power Distribution 152316 E1
Schematics
152315 Rev C
Appendix A
152315 Rev C
Schematics
Appendix A
Figure A-4 PV100S-480 Schematic for Converter Control Unit 152316 E3
Schematics
152315 Rev C
Appendix A
Figure A-5 PV100S-208 Schematic Main Power Distribution 152376 C1
Schematics
Appendix A
152315 Rev C
Appendix A
Schematics
152315 Rev C
Figure A-7 PV100S-208 Schematic for Converter Control Unit 152376 C3
Schematics
Appendix A
152315 Rev C
Schematics
This page was intentionally left blank
A-10
152315 Rev C