Introduction
System Specifications
The PV100S has been designed for photovoltaic power systems, which operate within the following specifications.
CAUTION: Equipment Damage
Operation of the PV100S in a manner other than specified in this manual may cause damage to the PV100S and other system components and will void the terms of the warranty.
Electrical Specifications
Table
Table 1-1 Electrical Specifications
Specification |
|
|
|
|
|
Nominal AC Input Voltage | 208 Vac | 480 Vac |
(+10% to | (183 to 228 Vac) | (422 to 528 Vac) |
Maximum AC Output Current | 278 Arms | 121 Arms |
Nominal AC Input Frequency | 60 Hz | 60 Hz |
(+0.5 to | (59.3 to 60.5 Hz) | (59.3 to 60.5 Hz) |
Output Power | 100.0 kW | 100.0 kW |
Peak Power Tracking Window | 330 to 600 Vdc | 330 to 600 Vdc |
Maximum Open Circuit Voltage | 600 Vdc | 600 Vdc |
Maximum DC Input Current | 319 amps | 319 amps |
|
|
|
Over Voltage, Under Voltage and Frequency Ranges
Table
Table 1-2 Over/Under Voltage and Over/Under Frequency Ranges
|
|
| ||||
Vac Condition |
|
|
|
|
|
|
|
|
|
|
|
| |
(% of Nominal) | Voltage Range | Trip Time | Voltage Range | Trip Time | ||
|
|
|
|
| ||
Vac < 50% | Vac < 104 | 6 cycles | Vac < 240 | 6 cycles | ||
50% < Vac < 88% | 104 | < Vac < 183 | 2 seconds | 240 | < Vac < 422 | 2 seconds |
88% < Vac < 110% | 183 | < Vac < 228 | normal operation | 422 | < Vac < 528 | normal operation |
110% < Vac < 137% | 228 | < Vac < 285 | 2 seconds | 528 | < Vac < 657 | 2 seconds |
137% < Vac | 285 | < Vac | 2 cycles | 657 | < Vac | 2 cycles |
f < rated | f < 59.3 | 6 cycles | f < 59.3 | 6 cycles | ||
f > rated +0.5 | f > 60.5 | 6 cycles | f > 60.5 | 6 cycles |
152315 Rev C |