Operator Interface Controls
Operator Interface Controls
Operator interface controls are located on the front door of the main inverter enclosure. These controls include an ON/OFF Switch,
AC Disconnect
Switch
Communication
Enclosure
LCD
Display
Universal Frontpanel Control (UFCP)
ON/OFF
Switch
DC Disconnect
Switch
DC Interface Enclosure
AC Interface Enclosure | Main Inverter Enclosure |
(AC Side View) | (Front View) |
Figure 1-2 PV100S Operator Interface Components
Main Enclosure Door Interlock Switch
The front door of the PV100S main enclosure is equipped with an interlock switch to preclude operation while the front door is open. Opening the door of the main inverter enclosure will initiate an immediate controlled shutdown of the PV100S and opens both the main AC and DC contactors. The main AC and DC contactors cannot be closed unless the door’s interlock is in the engaged position. The PV100S is prevented from being restarted until the door is again closed and the switch is in the engaged position.
It is required that the PV100S main enclosure door must be locked during normal operation. The door interlock switch does NOT remove all hazardous voltages from inside the inverter. Before attempting to service the PV100S, follow the
152315 Rev C |