To connect the main inverter to AC interface/transformer assembly
Operational Safety Procedures
System Status and Fault Reporting
A phase
Safety
Page 3
Image 3
PV100S 100 kW
Grid-Tied
Photovoltaic Inverter
Planning and Installation Manual
Page 2
Page 4
Page 3
Image 3
Page 2
Page 4
Contents
Planning and Installation Manual
PV100S 100 kW Grid-Tied Photovoltaic Inverter
PV100S-208 PV100S-480
Page
PV100S 100 kW Grid-Tied Photovoltaic Inverter
Planning and Installation Manual
Disclaimer
About Xantrex
Trademarks
Notice of Copyright
Audience
About This Manual
Purpose
Scope
Conventions Used
Related Information
Abbreviations and Acronyms
Page
WARNING Lethal Voltage
Important Safety Instructions
SAVE THESE INSTRUCTIONS - DO NOT DISCARD
WARNING Shock Hazard
Wiring Requirements
General Safety Precautions
Personal Safety
Safety Equipment
CAUTION Fire Hazard
Operational Safety Procedures
Lockout and Tag
WARNING Shock Hazard
De-Energize/Isolation Procedure
Interconnection Standards Compliance
To isolate the PV100S
Page
Contents
1 Introduction
2 Planning
Verification Procedure Summary
3 Installation
A Schematics
4 Verification
Tables
Page
Figures
Figure 3-18 AC Terminal Connections from the Utility- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -3-18 Figure 3-19 PV Array Cable Routing and Terminations - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -3-19 Figure 3-20 Telephone Cable Routing - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -3-21 Figure 3-21 RS232/FO Converter Kit Installation- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -3-23 Figure 3-22 Direct Connect Installation - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -3-24 Figure A-1 Electrical Diagram sample- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - A-3 Figure A-2 PV100S-480 Schematic for Main Power Distribution 152316 E1 - - - - - - - - - - - - - - A-4 Figure A-3 PV100S-480 Schematic for Control Power Distribution 152316 E2 - - - - - - - - - - - - - A-5 Figure A-4 PV100S-480 Schematic for Converter Control Unit 152316 E3- - - - - - - - - - - - - - - - A-6 Figure A-5 PV100S-208 Schematic Main Power Distribution 152376 C1 - - - - - - - - - - - - - - - - - A-7 Figure A-6 PV100S-208 Schematic for Control Power Distribution 152376 C2 - - - - - - - - - - - - - A-8 Figure A-7 PV100S-208 Schematic for Converter Control Unit 152376 C3- - - - - - - - - - - - - - - - A-9
1 Introduction
Description of the PV100S
59 ¼ 148 cm
Figure 1-1 Dimensions Not to scale
49 7/8 124.8 cm
60 ¼ 150.5 cm
Over Voltage, Under Voltage and Frequency Ranges
System Specifications
Electrical Specifications
CAUTION Equipment Damage
CAUTION Equipment Damage
System Ground Requirements
System Neutral Requirements
Utility Side Isolation Transformer Requirements
In front of access panels 36 in 91 cm
Environmental Specifications
Table 1-3 Environmental Specifications
In front of access doors 36 in 91 cm
Operator Interface Controls
Main Enclosure Door Interlock Switch
WARNING Shock Hazard
On/Off Switch
Figure 1-3 On/Off Switch
WARNING Shock Hazard
AC and DC Disconnect Switches
Communication Features
Data Logging
System Status and Fault Reporting
Universal Front Panel Control Unit UFCU
Communication Methods
PC Connection Methods
POTS Access
Wireless Access
Figure 1-7 POTS Access
Figure 1-10 Direct Access
Ethernet LAN Access
Direct Access
Figure 1-9 Ethernet LAN Access
2 Planning
WARNING Shock Hazard
Overview of PV100S Installation
PV Planning
Ventilation and Serviceability Requirements
Utility Side Isolation Transformer Requirements
Ground Requirements
System Neutral Requirements
Communication Requirements
Model PV100S-480
Electrical Diagrams and Schematics
CAUTION Equipment Damage
WARNING Lethal Voltage
Figure 2-1 PV100S Layout Option A
Layout Options
Figure 2-2 PV100S Layout Option B
Minimum Dimension of Base Approximately 9 ft by 7 ft 2.7 m x 2.1 m
Figure 2-3 Conduit Entry Figure Reference
Conduit Penetration
12 30 cm
6 15 cm 2 5 cm 12 30 cm
6 15 cm
2 5 cm 6 15 cm
Figure 2-6 AC Interface Enclosure Conduit Entry, Left Side
Figure 2-7 DC Interface Enclosure, Bottom Side
Figure 2-8 Communications Enclosure Conduit Entry, Bottom Side
Step 1. Determine the required cable ampacity
Conductor and Conduit Sizing
CAUTION Equipment Damage
To calculate the proper conduit size
DLO 3/0 AWG Cable
Sense/Control Wires
Step 3. Size the cable
Step 4. Size the conduit
16 ¼ 40.6 cm
Anchoring the PV100S
29 73.7 cm
5/8 1.5 cm x4
Planning
Figure 2-10 AC Interface/Transformer Anchor Bolt Pattern Not to Scale
17 ½73.7 cm 44 cm
63.5 cm ¾ 1.9 cm x6
3 Installation
Equipment Required
Unloading
WARNING Heavy Equipment
To move the PV100S while it is still inside the shipping crates
Moving the PV100S
Unpacking the PV100S
CAUTION Equipment Damage
Lift Here
Removing the Pallet and Moving the PV100S CAUTION Equipment Damage
Lift Here
To move the PV100S using a forklift
To mount and anchor the PV100S
Mounting and Anchoring the Units
To lock or unlock the front door on the main inverter
Opening or Closing Access Doors
Figure 3-4 Inverter Enclosure Access Doors
Installation
To Open Access Door
To Open Access Door
To Close Access Door
Figure 3-5 AC Interface Access Door
Transformer Access Panel
Figure 3-7 Transformer Access Panels
Figure 3-8 Inductor Access Panels
Installation
To install the conduits
Conduit Installation
CAUTION Equipment Damage
Wiring - General
WARNING Shock Hazard
WARNING Lethal Voltage
See Figure 3-14 on page 3-15 for the location of these terminals
Overcurrent Protection
Conductor Termination
CAUTION Equipment Damage
Grounding
Wire Gauge and Torque Requirements
System Neutral Requirements
Utility Side Isolation Transformer Requirements
Figure 3-11 Chassis Ground Bar TB1
CAUTION Equipment Damage
Wiring - Specific
AC Connections
To connect the main inverter to AC interface/transformer assembly
Transformer Enclosure
Figure 3-13 Tie-wraps on the AC Sense Harness
Figure 3-15 AC Terminal Connections in the Main Inverter Enclosure
A phase
C phase
B phase
CAUTION Equipment Damage
To connect the utility service to AC Interface Enclosure
Figure 3-18 AC Terminal Connections from the Utility
S1-2T1 A Phase terminal
S1-6T3 C Phase terminal
S1-4T2 B Phase terminal TB6 Neutral Ground TB2
Figure 3-19 PV Array Cable Routing and Terminations
PV Array Connections
PC Connection Methods
PC Communications
To connect a personal computer using the POTS Connection
Establishing a POTS Connection
To connect a personal computer using the Ethernet LAN Connection
Establishing Wireless Connection
Establishing an Ethernet LAN Connection
To connect a personal computer using the GSM Wireless modem
If connecting the PC directly to the inverter
Direct Connection
152315 Rev C
Figure 3-22 Direct Connect Installation
Installation
3-24
4 Verification
WARNING Shock Hazard
Verification Procedure Summary
WARNING Electrocution Hazard
Inspect the following items prior to completion of the installation
To perform a visual inspection of the PV100S electrical connections
Visual Inspection of Mechanical Connections
Visual Inspection of Electrical Connections
To perform a visual inspection of the PV100S mechanical connections
Perform after initial inspection if required
Visual Inspection, Isolation Transformer Wye/Wye
Corrective Action
To perform a visual inspection of the Isolation Transformer Wye/Wye
Appendix A contains useful schematics to aid with installation
A Schematics
This page intentionally left blank
Schematics
152315 Rev C
152315 Rev C
Figure A-1 Electrical Diagram sample
Schematics
Appendix A
Appendix A
Figure A-2 PV100S-480 Schematic for Main Power Distribution 152316 E1
Schematics
152315 Rev C
Schematics
Appendix A
152315 Rev C
Appendix A
Figure A-4 PV100S-480 Schematic for Converter Control Unit 152316 E3
Schematics
152315 Rev C
152315 Rev C
Figure A-5 PV100S-208 Schematic Main Power Distribution 152376 C1
Schematics
Appendix A
Schematics
152315 Rev C
Appendix A