Chapter 2 -
2.3 Presetting the field supply unit
Make sure that existing supply voltages for power section, field supply unit (field ex- citer) and field winding, fan, etc. match the rated data of the components used.
Switch ON power.
DANGER: System components now energized!
Please wait a few moments. During this time, the unit compares the phase sequence set in the parameter with that obtaining at the power section.
If the unit outputs the "Phase sequence fault of power section“ signalF( 38):
-switch off unit completely and disconnect from the mains, interchange two phases at the input, and start again from the beginning of this chapter.
or
- enter: 506 =
Unit will automatically adapt to phase sequence; this signal is to be interpreted as in- formation to the effect that the fans' direction of rotation may be wrong for
Only for uncontrolled field supply with
505 = 1 | Panel display: DIODE FIELD EXCIT |
Check field current and field voltage by measuring them.
Switch OFF power!
11202 = SAVE MOT1 SET
Save the altered values in the
Continue with Chapter 2.4
Only for controlled field supply with
505 | = 2 | Panel display: FEX2 OR FEX3 |
503 | = Rated motor field current |
Scales all parameters referenced to the motor field current, such as field cur- rent limitation or field current monitoring
1305 = Field current for "Under-excitation" signal
Check field current and field voltage by measuring them; if necessary, correct field current with 503.