3.14 Running the Drive

Operational Com- mand Keys

Chapter 3 - Handling of Control Panel CDP 31x

Operational commands can be given from the Control Panel CDP31x every time when the status row is displayed. Operational commands include START and STOP of the the drive, controlling the main contactor and adjusting the reference.

CAUTION! To be able to give operational commands from the CDP31x, the selected control location must be the Control Panel. The control location can be changed by means of LOC/REM key to LOCAL mode.

If LOC is activated some of the

binary inputs are no longer functioning.

Take care that the drive is engineered to allow opera- tion with LOCAL mode.

Control

Name of Key

Function

Panel Key

 

 

 

 

 

LOC

LOCAL /

To select LOCAL (= CDP31x) or REMOTE

 

REMOTE

(= ext. control system) operation.

 

 

 

 

START

Starts the drive, when in LOCAL mode.

 

 

 

 

STOP

Stops the drive, when in LOCAL mode.

 

 

 

 

ON

Main contactor closing control, when in

 

 

LOCAL mode.

 

 

 

 

OFF

Main contactor opening control, when in

 

 

LOCAL mode.

 

 

 

Running the DC-

Drive from the CDP31x

M

Ensure safety before you start the drive test!

Select LOCAL mode (LOCAL = CDP31x) by pressing LOC/REMOTE key.

Close (switch on) the main contactor by pressing the ON key

Start the drive by pressing the START key. Motor will now ac- celerate to the value of the reference.

Direction of rotation can be changed by giving the opposite po- larity reference value in case of 4Q drive.

Stop the drive by pressing the STOP key. Motor will decelerate to zero speed. (depending on the STOP MODE)

Finally open (switch off) the main contactor by pressing the OFF key.

DCS 500B / DCP 500B Operating Instructions

IV A 3 - 15

3ADW000055R0401_DCS500B_Operating Instruction_e_d

Image 51
Contents DCS 500B / DCF 500B DCP 500B How the DCS 500 Documentation System works Operating Instructions DCS 500B / DCP 500B Operating Instructions Overview Safety InstructionsSafety Instructions Mains connection Emergency Stop buttons Intended use Contents Signals and Troubleshooting DCS 500B / DCP 500B Operating Instructions Associated publications How to use this manualContents of this manual Target groupIncoming inspection Storage and transportRating plate = Line voltage General notesHow this chapter is structured Recommended motor voltages and field voltagesMethod of functioning of the binary inputs DI5, DI7 and DI8 System-dependent planning Symbols for enabling / disabling the referenceSymbol for measuring physical variables Symbol for displaying parameter values or connectionsPreparatory work Scaling intra-unit signals 11202 = Save MOT1 SET 518 = 500 V fixed! rated power converter voltageSet this only for units of the DCP 500 series 5191305 = Field current for Under-excitation signal Presetting the field supply unitIV a 2 1201 = 3 Panel display ARM. Autotuning Adjusting the current controllerDCS 500B / DCP 500B Operating Instructions IV a 2 Speed feedback balancing Only when the e.m.f. signal is being used as speed feedback Continue with Chapter Balancing the field supply unit and the e.m.f. controllerField weakening control with setting range 1 If the field time constant is not known 1204 = 1205 =11209 = 1009 = 1010 = 1201 = 0 Panel display not Activated 11202 = Save MOT1 SET1002 = 1004 == decrease so that motor voltage is 40% 11003= decrease so that motor voltage is 70% Proceed as described in 1. / 2. / 3. above12516 = increase slowly up to 20000 =100 % speed Only if analog tacho is used as speed feedback1008 = desired response behaviour of controller 1708 = 0,1 s 1709 = 0,1 s1204 POT1 = 10%...20% max. speed 408 = desired response behaviour of controller1204 = 1205 = Presetting the 3-phase field supply unit DCF 50xB 3603 = 1201 = 5Panel display FEX2/3 Autotuning3601 = 3602 =1201 = 4Panel display ARM. MAN. Tuning ⇒ CDP ⇒ CDP 310 or CDPID-NUMBER Total 1 Drives Start ModePanel Functions ACTPAR Pin/Parameter Selecting and Changing of Value Drive ModeValue To enter the Parameter ModeBackupstoremode Saving of the Parameters to backup memoryDisplay Mode Fault Resetting ResetFault History Display DCS Uploading and Downloading of Parameters UPLOAD/DOWNLOADDCS 500B / DCP 500B Operating Instructions IV a 3 Setting of the Display Contrast Full Name of output pinsDisplay Mode release key Selecting output pins Drive Mode Operational Com- mand Keys Running the DriveMode Speed Reference Setting for the DriveTo enter the Reference Setting To exit the Reference SettingDisplay of status, alarm and fault signals Signals and TroubleshootingGeneral messages Starting errors EAuxil. undervoltage Fault Signals FConv.fan curr.fault Earth faultMotor 1 overtemp SDCS-IOB-3, SDCS-POW P418Limited by the activation of a free wheeling Circuit Ext.Overvolt.FaultLocal & discon NectedField ex.1 comerror Mains overvoltageCheck Parameters of Field Exciter Arm. curent ripple Field ex.1 not OK See Fault Code FNo ext. FAN ack No main cont. ackIV a 4 Current Difference Reversal Fault101 Start inhibition Alarm Signals a103 Motor 1 temp. alarm Check See Fault Code F 105 Conv. overtemp120 108110 118130 127128 129138 134136 137At Macro x, macro-specific links or function 11201 Status SignalsBackupstoremode Fexcstatus 1120311205 11204DCF 500B IV a a IV a a 055R0401A2440000