Chapter 2 - Start-Up Instructions

2.6 Balancing the field supply unit and the e.m.f. controller

When matching the field supply unit to the system conditions, differences in the proce- dures adopted must be taken into account; these different procedures result from the op- erating mode used. Only the work of that section has to be performed which deals with the operating mode actually used in your system!

Constant field current control

Section 2.6.1

Field weakening control with setting range smaller than 1 : 1.5

Section 2.6.2

Field weakening control with setting range larger than 1 : 1.5

Section 2.6.3

2.6.1 Constant field current control

 

 

Switch ON power; start drive.

 

 

DANGER: System components now energized!

 

 

Drive should run up to 10 % of the speed.

 

 

12516 = increase slowly!

Internal reference value is increased; scaling: 20000 corresp. to 100 % speed or motor voltage, defined with P 501.

Measure motor voltage with the U ARM AC signal by changing between MODE ACT and PAR; with a value set with P 501, it must remain constant, or must not exceed this value if 12516 = 20000.

The motor voltage must not exceed the recommended motor voltage; see General notes at the beginning of this chapter.

Measure speed with manual tacho;

check rated speed when an analog tacho is being used; if necessary, correct with R9, R48 or R2716.

12516 = 0

Switch OFF power, thus stopping the drive!

Continue with Chapter 2.7

IV A 2 - 14

DCS 500B / DCP 500B Operating Instructions

3ADW000055R0401_DCS500B_Operating Instruction_e_d

Image 26
Contents DCS 500B / DCF 500B DCP 500B How the DCS 500 Documentation System works Operating Instructions DCS 500B / DCP 500B Operating Instructions Safety Instructions OverviewSafety Instructions Mains connection Emergency Stop buttons Intended use Contents Signals and Troubleshooting DCS 500B / DCP 500B Operating Instructions Target group How to use this manualContents of this manual Associated publicationsRating plate Incoming inspectionStorage and transport Recommended motor voltages and field voltages General notesHow this chapter is structured = Line voltageMethod of functioning of the binary inputs DI5, DI7 and DI8 Symbols for enabling / disabling the reference System-dependent planningSymbol for displaying parameter values or connections Symbol for measuring physical variablesPreparatory work Scaling intra-unit signals 519 518 = 500 V fixed! rated power converter voltageSet this only for units of the DCP 500 series 11202 = Save MOT1 SETPresetting the field supply unit 1305 = Field current for Under-excitation signalIV a 2 Adjusting the current controller 1201 = 3 Panel display ARM. AutotuningDCS 500B / DCP 500B Operating Instructions IV a 2 Speed feedback balancing Only when the e.m.f. signal is being used as speed feedback Balancing the field supply unit and the e.m.f. controller Continue with ChapterField weakening control with setting range 1 11209 = If the field time constant is not known1204 = 1205 = 1004 = 1201 = 0 Panel display not Activated 11202 = Save MOT1 SET1002 = 1009 = 1010 =Proceed as described in 1. / 2. / 3. above 11003= decrease so that motor voltage is 70% = decrease so that motor voltage is 40%Only if analog tacho is used as speed feedback 12516 = increase slowly up to 20000 =100 % speed408 = desired response behaviour of controller 1708 = 0,1 s 1709 = 0,1 s1204 POT1 = 10%...20% max. speed 1008 = desired response behaviour of controller1204 = 1205 = Presetting the 3-phase field supply unit DCF 50xB 3602 = 1201 = 5Panel display FEX2/3 Autotuning3601 = 3603 =1201 = 4Panel display ARM. MAN. Tuning ⇒ CDP 310 or CDP ⇒ CDPStart Mode ID-NUMBER Total 1 DrivesACT Panel FunctionsPAR Drive Mode Pin/Parameter Selecting and Changing of ValueTo enter the Parameter Mode ValueSaving of the Parameters to backup memory BackupstoremodeFault Resetting Reset Display ModeFault History Display Uploading and Downloading of Parameters UPLOAD/DOWNLOAD DCSDCS 500B / DCP 500B Operating Instructions IV a 3 Display Mode release key Setting of the Display ContrastFull Name of output pins Selecting output pins Drive Mode Running the Drive Operational Com- mand KeysTo exit the Reference Setting Speed Reference Setting for the DriveTo enter the Reference Setting ModeSignals and Troubleshooting Display of status, alarm and fault signalsStarting errors E General messagesFault Signals F Auxil. undervoltageMotor 1 overtemp Conv.fan curr.faultEarth fault P418 SDCS-IOB-3, SDCS-POWNected Ext.Overvolt.FaultLocal & discon Limited by the activation of a free wheeling CircuitCheck Parameters of Field Exciter Field ex.1 comerrorMains overvoltage Arm. curent ripple No main cont. ack See Fault Code FNo ext. FAN ack Field ex.1 not OKIV a 4 Reversal Fault Current DifferenceCheck See Fault Code F 105 Conv. overtemp Alarm Signals a103 Motor 1 temp. alarm 101 Start inhibition118 108110 120129 127128 130137 134136 138At Macro x, macro-specific links or function Status Signals 11201Backupstoremode 11203 Fexcstatus11204 11205DCF 500B IV a a IV a a 055R0401A2440000