DCS 500 manual Status Signals, 11201

Page 69

Chapter 4 - Signals and Troubleshooting

4.6 Status Signals

The status of drive functions (autotuning of controllers; saving val- ues) is shown by status signals named 11201 and 11202. The status of the first and / or the second field exciter, the torque control sequencing and the current controller is shown by the signals 11203 to 11205.

In case of a drive function, which is started by setting a parameter to a defined value the status is indicated automatically on the LCD display of the panel CDP 31x in plain text. The indication will show the result directly or will cross-reference to the final location.

The status of the field exciter(s), torque control and current control- ler is updated regularly by the converter software and can be checked if one of the three signals is selected.

Depending on the tool in use (CDP 31x or CMT tool) the plain text or a number appears on the display / screen. This number repre- sents a code which is equivalent to the plain text for signal 11201; for all others it´s a binary coded decimal number (the 16 bit word with the binary value for each signals is transferred to decimal).

 

Para-

 

 

Code

 

 

Text on LCD of con-

 

 

Definition / explication of the signal

 

 

Remark

 

 

 

 

/

 

 

 

 

 

 

 

 

meter

 

 

 

 

trol panel CDP 31x

 

 

 

 

 

 

 

 

 

 

bit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

11201

--

----

 

 

COMMIS_STAT:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Result from a drive function. Gives feedback status

 

 

 

 

 

 

 

 

 

 

 

 

 

 

information when the DRIVEMODE parameter (1201)

 

 

 

 

 

 

 

 

 

 

 

was used to start a drive function.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

 

NOT ACTIVATED

 

 

selected function successfully worked out

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

RUN COMMAND ?

 

 

see code 53

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

FEXC SEL ?

 

 

wrong FEX selection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

FEXC RDY OPER=0

 

 

FEX1 / 2 or DCF 503/4 not ready for operation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

FEXC OK=0

 

 

field supply not o.k.; see error message on the dis-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

play of the converter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

 

FIELD ON=0

 

 

FEX1 / 2 or DCF 503/4 not switched on

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

 

IF NOT IN 95–105%

 

 

field current not within 95% ..... 105%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

 

NOT O.K.AFTER 20s

 

 

drive was not released by hardware within 20s

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8

 

reserved

 

 

up to 34

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

35

 

CANNOT AUTOTUNE

 

 

cannot autotune the armature current controller

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

36

 

reserved

 

 

up to 48

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

49

 

IF AT START ?

 

 

Field current does not reach reference within 10s,

 

 

 

 

 

 

 

 

 

 

 

 

 

 

when the selftuning is started

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DCS 500B / DCP 500B Operating Instructions

IV A 4 - 17

3ADW000055R0401_DCS500B_Operating Instruction_e_d

Image 69
Contents DCS 500B / DCF 500B DCP 500B How the DCS 500 Documentation System works Operating Instructions DCS 500B / DCP 500B Operating Instructions Overview Safety InstructionsSafety Instructions Mains connection Emergency Stop buttons Intended use Contents Signals and Troubleshooting DCS 500B / DCP 500B Operating Instructions Contents of this manual How to use this manualTarget group Associated publicationsIncoming inspection Storage and transportRating plate How this chapter is structured General notesRecommended motor voltages and field voltages = Line voltageMethod of functioning of the binary inputs DI5, DI7 and DI8 System-dependent planning Symbols for enabling / disabling the referenceSymbol for measuring physical variables Symbol for displaying parameter values or connectionsPreparatory work Scaling intra-unit signals Set this only for units of the DCP 500 series 518 = 500 V fixed! rated power converter voltage519 11202 = Save MOT1 SET1305 = Field current for Under-excitation signal Presetting the field supply unitIV a 2 1201 = 3 Panel display ARM. Autotuning Adjusting the current controllerDCS 500B / DCP 500B Operating Instructions IV a 2 Speed feedback balancing Only when the e.m.f. signal is being used as speed feedback Continue with Chapter Balancing the field supply unit and the e.m.f. controllerField weakening control with setting range 1 If the field time constant is not known 1204 = 1205 =11209 = 1002 = 1201 = 0 Panel display not Activated 11202 = Save MOT1 SET1004 = 1009 = 1010 == decrease so that motor voltage is 70% 11003Proceed as described in 1. / 2. / 3. above = decrease so that motor voltage is 40%12516 = increase slowly up to 20000 =100 % speed Only if analog tacho is used as speed feedback1204 POT1 = 10%...20% max. speed 1708 = 0,1 s 1709 = 0,1 s408 = desired response behaviour of controller 1008 = desired response behaviour of controller1204 = 1205 = Presetting the 3-phase field supply unit DCF 50xB 3601 = 1201 = 5Panel display FEX2/3 Autotuning3602 = 3603 =1201 = 4Panel display ARM. MAN. Tuning ⇒ CDP ⇒ CDP 310 or CDPID-NUMBER Total 1 Drives Start ModePanel Functions ACTPAR Pin/Parameter Selecting and Changing of Value Drive ModeValue To enter the Parameter ModeBackupstoremode Saving of the Parameters to backup memoryDisplay Mode Fault Resetting ResetFault History Display DCS Uploading and Downloading of Parameters UPLOAD/DOWNLOADDCS 500B / DCP 500B Operating Instructions IV a 3 Setting of the Display Contrast Full Name of output pinsDisplay Mode release key Selecting output pins Drive Mode Operational Com- mand Keys Running the DriveTo enter the Reference Setting Speed Reference Setting for the DriveTo exit the Reference Setting ModeDisplay of status, alarm and fault signals Signals and TroubleshootingGeneral messages Starting errors EAuxil. undervoltage Fault Signals FConv.fan curr.fault Earth faultMotor 1 overtemp SDCS-IOB-3, SDCS-POW P418Local & discon Ext.Overvolt.FaultNected Limited by the activation of a free wheeling CircuitField ex.1 comerror Mains overvoltageCheck Parameters of Field Exciter Arm. curent ripple No ext. FAN ack See Fault Code FNo main cont. ack Field ex.1 not OKIV a 4 Current Difference Reversal Fault103 Motor 1 temp. alarm Alarm Signals aCheck See Fault Code F 105 Conv. overtemp 101 Start inhibition110 108118 120128 127129 130136 134137 138At Macro x, macro-specific links or function 11201 Status SignalsBackupstoremode Fexcstatus 1120311205 11204DCF 500B IV a a IV a a 055R0401A2440000