Chapter 3 - Handling of Control Panel CDP 31x

3.9 Uploading and Downloading of Parameters (UPLOAD/DOWNLOAD)

CAUTION! The drive must be in standstill condition with given STOP command (controllers blocked, power section disconnected from the network) when UPLOAD/ DOWNLOAD function is selected.

 

 

DCS 500

FPROM = FLASH-PROM

 

Parameter 11202:

RAM = Random Access Memory

Control

1 = SAVE MOT1 SET

 

 

 

Panel

2 = SAVE MOT2 SET

FPROM D35

 

 

 

 

 

 

 

 

FPROM D33&34

FACTORY-

Parameter 11202:

 

 

4 =SELECT MOT1 SET

 

 

 

SET VALUE

FPROM

UPLOAD

 

5 =SELECT MOT2 SET

RAM

 

 

 

 

 

 

 

DOWNLOAD

 

 

 

If one or both of these functions have been performed additional ac- tions may be needed. For example BACKUPSTOREMODE should be selected for saving the values to the backup memory, if a DOWNLOAD had taken place.

UPLOAD will copy all parameters and connections, which are dif- ferent to default, from the RAM memory of the drive to the FPROM memory of the Control Panel CDP 31x.

Before a DOWNLOAD is started the factory-set values (default val- ues) should be available within the drive´sRAM memory. Factory-set values are always available in control board memory and they can be called by means of BACKUPSTOREMODE pa- rameter 11202 [FACTORY_SET_VALUE] or by means of S2 switch on the control board SDCS-CON-x.

The DOWNLOAD will copy all values stored in the FPROM memory of the CDP 31x to the RAM memory of the drive. Downloaded parameters should be saved to the FPROM memory of the control board SDCS-CON-x. See chapter 3.5"Saving of Parameters to backup memory" .

Note: For reasons of safety the DOWNLOAD function will only operate if „LOCAL mode“ of the Control Panel CDP 31x is selected!

IV A 3 - 10

DCS 500B / DCP 500B Operating Instructions

3ADW000055R0401_DCS500B_Operating Instruction_e_d

Image 46
Contents DCS 500B / DCF 500B DCP 500B How the DCS 500 Documentation System works Operating Instructions DCS 500B / DCP 500B Operating Instructions Safety Instructions OverviewSafety Instructions Mains connection Emergency Stop buttons Intended use Contents Signals and Troubleshooting DCS 500B / DCP 500B Operating Instructions Target group How to use this manualContents of this manual Associated publicationsStorage and transport Incoming inspectionRating plate Recommended motor voltages and field voltages General notesHow this chapter is structured = Line voltageMethod of functioning of the binary inputs DI5, DI7 and DI8 Symbols for enabling / disabling the reference System-dependent planningSymbol for displaying parameter values or connections Symbol for measuring physical variablesPreparatory work Scaling intra-unit signals 519 518 = 500 V fixed! rated power converter voltageSet this only for units of the DCP 500 series 11202 = Save MOT1 SETPresetting the field supply unit 1305 = Field current for Under-excitation signalIV a 2 Adjusting the current controller 1201 = 3 Panel display ARM. AutotuningDCS 500B / DCP 500B Operating Instructions IV a 2 Speed feedback balancing Only when the e.m.f. signal is being used as speed feedback Balancing the field supply unit and the e.m.f. controller Continue with ChapterField weakening control with setting range 1 1204 = 1205 = If the field time constant is not known11209 = 1004 = 1201 = 0 Panel display not Activated 11202 = Save MOT1 SET1002 = 1009 = 1010 =Proceed as described in 1. / 2. / 3. above 11003= decrease so that motor voltage is 70% = decrease so that motor voltage is 40%Only if analog tacho is used as speed feedback 12516 = increase slowly up to 20000 =100 % speed408 = desired response behaviour of controller 1708 = 0,1 s 1709 = 0,1 s1204 POT1 = 10%...20% max. speed 1008 = desired response behaviour of controller1204 = 1205 = Presetting the 3-phase field supply unit DCF 50xB 3602 = 1201 = 5Panel display FEX2/3 Autotuning3601 = 3603 =1201 = 4Panel display ARM. MAN. Tuning ⇒ CDP 310 or CDP ⇒ CDPStart Mode ID-NUMBER Total 1 DrivesACT Panel FunctionsPAR Drive Mode Pin/Parameter Selecting and Changing of ValueTo enter the Parameter Mode ValueSaving of the Parameters to backup memory BackupstoremodeFault Resetting Reset Display ModeFault History Display Uploading and Downloading of Parameters UPLOAD/DOWNLOAD DCSDCS 500B / DCP 500B Operating Instructions IV a 3 Full Name of output pins Setting of the Display ContrastDisplay Mode release key Selecting output pins Drive Mode Running the Drive Operational Com- mand KeysTo exit the Reference Setting Speed Reference Setting for the DriveTo enter the Reference Setting ModeSignals and Troubleshooting Display of status, alarm and fault signalsStarting errors E General messagesFault Signals F Auxil. undervoltageEarth fault Conv.fan curr.faultMotor 1 overtemp P418 SDCS-IOB-3, SDCS-POWNected Ext.Overvolt.FaultLocal & discon Limited by the activation of a free wheeling CircuitMains overvoltage Field ex.1 comerrorCheck Parameters of Field Exciter Arm. curent ripple No main cont. ack See Fault Code FNo ext. FAN ack Field ex.1 not OKIV a 4 Reversal Fault Current DifferenceCheck See Fault Code F 105 Conv. overtemp Alarm Signals a103 Motor 1 temp. alarm 101 Start inhibition118 108110 120129 127128 130137 134136 138At Macro x, macro-specific links or function Status Signals 11201Backupstoremode 11203 Fexcstatus11204 11205DCF 500B IV a a IV a a 055R0401A2440000