Chapter 4 - Signals and Troubleshooting

Code

Text on

Definition /

Status

Remark

seven

LCD of control panel

Action

signal

 

segm.

CDP 31x

 

(FAULT_WORD_1/2)

 

display

 

 

 

 

 

 

F 28 Armature over-

Armature (DC circuit) overvoltage

11101 bit 2

(1)

voltage

Check: - Setting of param. [P 511] suitable

 

 

 

for the system configuration?

 

 

-Setting of field current and actual value as well as the complete field supply (FIELD EXCITER);

-Was the motor accelerated by the load?

-Speed scaling;

-Armature voltage feedback;

-Connections between SDCS- CON-x and SDCS-PIN boards;

-Coding of voltage evaluation on SDCS-PIN-xx board.

F 29 Mains undervoltage Mains supply undervoltage (AC); setting via

11101 bit 11

(3)

parameter [P 509]

 

 

Check: - Does the supply voltage exist?

 

 

-Did the mains contactor close?

-Setting of voltage feedback coding (voltage scaling) correct?

-Connections between SDCS- CON-x and SDCS-PIN-xx boards;

-Coding of voltage evaluation on SDCS-PIN-xx board.

F 30

Mains overvoltage

Mains supply overvoltage (AC)

11101

bit 12

(1)

 

 

Mains voltage > 130% of nominal value for

 

 

 

 

 

longer than 10s.

 

 

 

 

 

Fault tracing see Fault Code F 29.

 

 

 

 

 

 

 

 

 

F 31

Not in synchronism

Synchronization fault (of mains)

11101

bit 13

(3)

 

 

Check: - Mains supply, fuses etc.;

 

 

 

 

 

- Mains voltage and stability.

 

 

 

 

 

 

 

 

 

F 32

Field ex.1 overcurr

FIELD EXCITER 1 (field supply 1) overcurrent

11101

bit 14

(1)

 

 

Check: - Parameters of FIELD EXCITER 1;

 

 

 

-Connections of field exciter as well as insulation level of cable and of field winding.

F 33 Field ex.1 comerror

FIELD EXCITER 1 communication error

11101 bit 15

(1)

Check: - Flat cable connections X14: or cable X16: between SDCS- CON-x board and field exciter;

- Auxil. voltage for ext. field exciter.

DCS 500B / DCP 500B Operating Instructions

IV A 4 - 7

3ADW000055R0401_DCS500B_Operating Instruction_e_d

Image 59
Contents DCS 500B / DCF 500B DCP 500B How the DCS 500 Documentation System works Operating Instructions DCS 500B / DCP 500B Operating Instructions Overview Safety InstructionsSafety Instructions Mains connection Emergency Stop buttons Intended use Contents Signals and Troubleshooting DCS 500B / DCP 500B Operating Instructions Associated publications How to use this manualContents of this manual Target groupRating plate Incoming inspectionStorage and transport = Line voltage General notesHow this chapter is structured Recommended motor voltages and field voltagesMethod of functioning of the binary inputs DI5, DI7 and DI8 System-dependent planning Symbols for enabling / disabling the referenceSymbol for measuring physical variables Symbol for displaying parameter values or connectionsPreparatory work Scaling intra-unit signals 11202 = Save MOT1 SET 518 = 500 V fixed! rated power converter voltageSet this only for units of the DCP 500 series 5191305 = Field current for Under-excitation signal Presetting the field supply unitIV a 2 1201 = 3 Panel display ARM. Autotuning Adjusting the current controllerDCS 500B / DCP 500B Operating Instructions IV a 2 Speed feedback balancing Only when the e.m.f. signal is being used as speed feedback Continue with Chapter Balancing the field supply unit and the e.m.f. controllerField weakening control with setting range 1 11209 = If the field time constant is not known1204 = 1205 = 1009 = 1010 = 1201 = 0 Panel display not Activated 11202 = Save MOT1 SET1002 = 1004 == decrease so that motor voltage is 40% 11003= decrease so that motor voltage is 70% Proceed as described in 1. / 2. / 3. above12516 = increase slowly up to 20000 =100 % speed Only if analog tacho is used as speed feedback1008 = desired response behaviour of controller 1708 = 0,1 s 1709 = 0,1 s1204 POT1 = 10%...20% max. speed 408 = desired response behaviour of controller1204 = 1205 = Presetting the 3-phase field supply unit DCF 50xB 3603 = 1201 = 5Panel display FEX2/3 Autotuning3601 = 3602 =1201 = 4Panel display ARM. MAN. Tuning ⇒ CDP ⇒ CDP 310 or CDPID-NUMBER Total 1 Drives Start ModePanel Functions ACTPAR Pin/Parameter Selecting and Changing of Value Drive ModeValue To enter the Parameter ModeBackupstoremode Saving of the Parameters to backup memoryDisplay Mode Fault Resetting ResetFault History Display DCS Uploading and Downloading of Parameters UPLOAD/DOWNLOADDCS 500B / DCP 500B Operating Instructions IV a 3 Display Mode release key Setting of the Display ContrastFull Name of output pins Selecting output pins Drive Mode Operational Com- mand Keys Running the DriveMode Speed Reference Setting for the DriveTo enter the Reference Setting To exit the Reference SettingDisplay of status, alarm and fault signals Signals and TroubleshootingGeneral messages Starting errors EAuxil. undervoltage Fault Signals FMotor 1 overtemp Conv.fan curr.faultEarth fault SDCS-IOB-3, SDCS-POW P418Limited by the activation of a free wheeling Circuit Ext.Overvolt.FaultLocal & discon NectedCheck Parameters of Field Exciter Field ex.1 comerrorMains overvoltage Arm. curent ripple Field ex.1 not OK See Fault Code FNo ext. FAN ack No main cont. ackIV a 4 Current Difference Reversal Fault101 Start inhibition Alarm Signals a103 Motor 1 temp. alarm Check See Fault Code F 105 Conv. overtemp120 108110 118130 127128 129138 134136 137At Macro x, macro-specific links or function 11201 Status SignalsBackupstoremode Fexcstatus 1120311205 11204DCF 500B IV a a IV a a 055R0401A2440000