Chapter 2 -
2.2 Scaling intra-unit signals
Make sure that the existing electronics supply voltage has been set on the SDCS-
If an encoder is being used as the speed feedback device, make sure that the correct supply voltage has been seton the boards
| |
| |
Switch on the power supply to the electronics section. | |
The display of Panel CDP 31x | DCS 500 |
may show the following | ** WARNING ** |
information: | +Emergency stop |
|
|
522 = GERMAN [Only with the
501 = Rated motor voltage
This is used to scale those parameters referring to the rated motor voltage, such as field crossover point or maximum speed with e.m.f. control.
502 = Rated motor current
This is used to scale those parameters referring to the rated motor current, such as current limitation or torque limitation.
507 = Rated line voltage
This is used to scale those parameters referring to the line voltage, such as line undervoltage.
Only when connection diagram 1 (Appendix A) is being used!
906 = 12502
„Emergency Stop“
910 = 10908
No
911 = 10908
No acknowledge signal from motor fan necessary
Set this only for units with a rated current ≥ 2050A!
517 | = Rated power converter current |
|
Enter numerical value from rating plate here | ||
518 | = Rated power converter supply voltage | |
Enter numerical value from rating plate here | ||
519 | = 45 Grad Celsius |
|
Temperature monitoring of power section | ||
520 | = 4 ⇒ Size C4 has been selected |
|
Coding for unit type |
| |
521 | = 1 : Single bridge | ⇒ on rating plate: DCS 501 xxxx |
| 4 : Double bridge | ⇒ on rating plate: DCS 502 xxxx |
Coding for power section (bridge) type
IV A 2 - 6 | DCS 500B / DCP 500B Operating Instructions |
3ADW000055R0401_DCS500B_Operating Instruction_e_d