DCS 500 manual Scaling intra-unit signals

Page 18

Chapter 2 - Start-Up Instructions

2.2 Scaling intra-unit signals

Make sure that the existing electronics supply voltage has been set on the SDCS- POW-1 power supply board as well, using the SW1 switch.

If an encoder is being used as the speed feedback device, make sure that the correct supply voltage has been seton the boards

SDCS-POW-1: X3: / X4: / X5:

SDCS-IOB-3: S4

 

 

Switch on the power supply to the electronics section.

The display of Panel CDP 31x

DCS 500

may show the following

** WARNING **

information:

+Emergency stop

 

 

522 = GERMAN [Only with the SDCS-CON-2 control board & the CDP 312 panel!] Activates German texts on the display

501 = Rated motor voltage

This is used to scale those parameters referring to the rated motor voltage, such as field crossover point or maximum speed with e.m.f. control.

502 = Rated motor current

This is used to scale those parameters referring to the rated motor current, such as current limitation or torque limitation.

507 = Rated line voltage

This is used to scale those parameters referring to the line voltage, such as line undervoltage.

Only when connection diagram 1 (Appendix A) is being used!

906 = 12502

„Emergency Stop“ de-activated

910 = 10908

No check-back signal from unit fan necessary

911 = 10908

No acknowledge signal from motor fan necessary

Set this only for units with a rated current 2050A!

517

= Rated power converter current

 

Enter numerical value from rating plate here

518

= Rated power converter supply voltage

Enter numerical value from rating plate here

519

= 45 Grad Celsius

 

Temperature monitoring of power section

520

= 4 Size C4 has been selected

 

Coding for unit type

 

521

= 1 : Single bridge (2-Q) converter

on rating plate: DCS 501 xxxx

 

4 : Double bridge (4-Q) converter

on rating plate: DCS 502 xxxx

Coding for power section (bridge) type

IV A 2 - 6

DCS 500B / DCP 500B Operating Instructions

3ADW000055R0401_DCS500B_Operating Instruction_e_d

Image 18
Contents DCS 500B / DCF 500B DCP 500B How the DCS 500 Documentation System works Operating Instructions DCS 500B / DCP 500B Operating Instructions Safety Instructions OverviewSafety Instructions Mains connection Emergency Stop buttons Intended use Contents Signals and Troubleshooting DCS 500B / DCP 500B Operating Instructions Target group How to use this manualContents of this manual Associated publicationsIncoming inspection Storage and transportRating plate Recommended motor voltages and field voltages General notesHow this chapter is structured = Line voltageMethod of functioning of the binary inputs DI5, DI7 and DI8 Symbols for enabling / disabling the reference System-dependent planningSymbol for displaying parameter values or connections Symbol for measuring physical variablesPreparatory work Scaling intra-unit signals 519 518 = 500 V fixed! rated power converter voltageSet this only for units of the DCP 500 series 11202 = Save MOT1 SETPresetting the field supply unit 1305 = Field current for Under-excitation signalIV a 2 Adjusting the current controller 1201 = 3 Panel display ARM. AutotuningDCS 500B / DCP 500B Operating Instructions IV a 2 Speed feedback balancing Only when the e.m.f. signal is being used as speed feedback Balancing the field supply unit and the e.m.f. controller Continue with ChapterField weakening control with setting range 1 If the field time constant is not known 1204 = 1205 =11209 = 1004 = 1201 = 0 Panel display not Activated 11202 = Save MOT1 SET1002 = 1009 = 1010 =Proceed as described in 1. / 2. / 3. above 11003= decrease so that motor voltage is 70% = decrease so that motor voltage is 40%Only if analog tacho is used as speed feedback 12516 = increase slowly up to 20000 =100 % speed408 = desired response behaviour of controller 1708 = 0,1 s 1709 = 0,1 s1204 POT1 = 10%...20% max. speed 1008 = desired response behaviour of controller1204 = 1205 = Presetting the 3-phase field supply unit DCF 50xB 3602 = 1201 = 5Panel display FEX2/3 Autotuning3601 = 3603 =1201 = 4Panel display ARM. MAN. Tuning ⇒ CDP 310 or CDP ⇒ CDPStart Mode ID-NUMBER Total 1 DrivesACT Panel FunctionsPAR Drive Mode Pin/Parameter Selecting and Changing of ValueTo enter the Parameter Mode ValueSaving of the Parameters to backup memory BackupstoremodeFault Resetting Reset Display ModeFault History Display Uploading and Downloading of Parameters UPLOAD/DOWNLOAD DCSDCS 500B / DCP 500B Operating Instructions IV a 3 Setting of the Display Contrast Full Name of output pinsDisplay Mode release key Selecting output pins Drive Mode Running the Drive Operational Com- mand KeysTo exit the Reference Setting Speed Reference Setting for the DriveTo enter the Reference Setting ModeSignals and Troubleshooting Display of status, alarm and fault signalsStarting errors E General messagesFault Signals F Auxil. undervoltageConv.fan curr.fault Earth faultMotor 1 overtemp P418 SDCS-IOB-3, SDCS-POWNected Ext.Overvolt.FaultLocal & discon Limited by the activation of a free wheeling CircuitField ex.1 comerror Mains overvoltageCheck Parameters of Field Exciter Arm. curent ripple No main cont. ack See Fault Code FNo ext. FAN ack Field ex.1 not OKIV a 4 Reversal Fault Current DifferenceCheck See Fault Code F 105 Conv. overtemp Alarm Signals a103 Motor 1 temp. alarm 101 Start inhibition118 108110 120129 127128 130137 134136 138At Macro x, macro-specific links or function Status Signals 11201Backupstoremode 11203 Fexcstatus11204 11205DCF 500B IV a a IV a a 055R0401A2440000