Chapter 4 - Signals and Troubleshooting

 

Para-

 

 

Code

 

 

Text on LCD of con-

 

 

Definition / explication of the signal

 

 

Remark

 

 

 

 

/

 

 

 

 

 

 

 

 

meter

 

 

 

 

trol panel CDP 31x

 

 

 

 

 

 

 

 

 

 

bit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12

(FIELD2_CURR_MIN_L)

 

1

= motor 2 field current above min level

 

 

 

 

 

 

 

 

 

 

 

 

 

11204

--

----

 

TC_STATUS:

 

 

 

 

 

 

 

 

 

 

 

 

 

Status of the torque control sequencing

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

00

(RDY ON)

 

1

= ready for closing contractor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

01

(MAIN CONT ON)

 

1

= command to close contractor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

02

(RDY RUNNING)

 

1

= ready for run command

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

03

(RUNNING)

 

1

= command to release controllers

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

04

(TC_RDY_REF)

 

1

= ready for reference

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

05

(TC_FIELD_CHANGE)

 

1

= field reversal is active

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

06

(CONTINUOUS_CURR)

 

1

= armature current is discontinuous

 

 

 

 

 

 

 

 

 

 

 

 

 

11205

--

----

 

BC:

 

 

 

 

 

 

 

 

 

 

 

 

 

Status of the current regulator. If the value of BC is

 

 

 

 

 

 

 

 

 

 

 

 

 

zero, everything is OK. Otherwise different bits of

 

 

 

 

 

 

 

 

 

 

 

 

 

BC will indicate the reason for blocking the current

 

 

 

 

 

 

 

 

 

 

 

 

 

regulator

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

00

--------

 

Overcurrent

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

01

--------

 

Freewheeling unit was fired

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

02

--------

 

field reversal

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

03

--------

 

supply system undervoltage

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

04

--------

 

12Puls only: fault 65 and 66 occurred

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

05

--------

 

12Puls only: signal via cable X18

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

06

--------

 

supply system overvoltage

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

07

--------

 

type code error

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

08

--------

 

suppression of controller at regulator change-over

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

09

--------

 

processor overload

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

--------

 

thyristor diagnostic running

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

11

--------

 

--------

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12

--------

 

primary (AC) or secondary (48Vdc) power failure

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

--------

 

synchronization signal missing

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

14

--------

 

pulse firing section not in synchronism

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15

--------

 

not released

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IV A 4 - 20

DCS 500B / DCP 500B Operating Instructions

3ADW000055R0401_DCS500B_Operating Instruction_e_d

Image 72
Contents DCS 500B / DCF 500B DCP 500B How the DCS 500 Documentation System works Operating Instructions DCS 500B / DCP 500B Operating Instructions Safety Instructions OverviewSafety Instructions Mains connection Emergency Stop buttons Intended use Contents Signals and Troubleshooting DCS 500B / DCP 500B Operating Instructions How to use this manual Contents of this manualTarget group Associated publicationsIncoming inspection Storage and transportRating plate General notes How this chapter is structuredRecommended motor voltages and field voltages = Line voltageMethod of functioning of the binary inputs DI5, DI7 and DI8 Symbols for enabling / disabling the reference System-dependent planningSymbol for displaying parameter values or connections Symbol for measuring physical variablesPreparatory work Scaling intra-unit signals 518 = 500 V fixed! rated power converter voltage Set this only for units of the DCP 500 series519 11202 = Save MOT1 SETPresetting the field supply unit 1305 = Field current for Under-excitation signalIV a 2 Adjusting the current controller 1201 = 3 Panel display ARM. AutotuningDCS 500B / DCP 500B Operating Instructions IV a 2 Speed feedback balancing Only when the e.m.f. signal is being used as speed feedback Balancing the field supply unit and the e.m.f. controller Continue with ChapterField weakening control with setting range 1 If the field time constant is not known 1204 = 1205 =11209 = 1201 = 0 Panel display not Activated 11202 = Save MOT1 SET 1002 =1004 = 1009 = 1010 =11003 = decrease so that motor voltage is 70%Proceed as described in 1. / 2. / 3. above = decrease so that motor voltage is 40%Only if analog tacho is used as speed feedback 12516 = increase slowly up to 20000 =100 % speed1708 = 0,1 s 1709 = 0,1 s 1204 POT1 = 10%...20% max. speed408 = desired response behaviour of controller 1008 = desired response behaviour of controller1204 = 1205 = Presetting the 3-phase field supply unit DCF 50xB 1201 = 5Panel display FEX2/3 Autotuning 3601 =3602 = 3603 =1201 = 4Panel display ARM. MAN. Tuning ⇒ CDP 310 or CDP ⇒ CDPStart Mode ID-NUMBER Total 1 DrivesACT Panel FunctionsPAR Drive Mode Pin/Parameter Selecting and Changing of ValueTo enter the Parameter Mode ValueSaving of the Parameters to backup memory BackupstoremodeFault Resetting Reset Display ModeFault History Display Uploading and Downloading of Parameters UPLOAD/DOWNLOAD DCSDCS 500B / DCP 500B Operating Instructions IV a 3 Setting of the Display Contrast Full Name of output pinsDisplay Mode release key Selecting output pins Drive Mode Running the Drive Operational Com- mand KeysSpeed Reference Setting for the Drive To enter the Reference SettingTo exit the Reference Setting ModeSignals and Troubleshooting Display of status, alarm and fault signalsStarting errors E General messagesFault Signals F Auxil. undervoltageConv.fan curr.fault Earth faultMotor 1 overtemp P418 SDCS-IOB-3, SDCS-POWExt.Overvolt.Fault Local & disconNected Limited by the activation of a free wheeling CircuitField ex.1 comerror Mains overvoltageCheck Parameters of Field Exciter Arm. curent ripple See Fault Code F No ext. FAN ackNo main cont. ack Field ex.1 not OKIV a 4 Reversal Fault Current DifferenceAlarm Signals a 103 Motor 1 temp. alarmCheck See Fault Code F 105 Conv. overtemp 101 Start inhibition108 110118 120127 128129 130134 136137 138At Macro x, macro-specific links or function Status Signals 11201Backupstoremode 11203 Fexcstatus11204 11205DCF 500B IV a a IV a a 055R0401A2440000