Chapter 4 - Signals and Troubleshooting

4.4 Fault Signals (F)

The fault signals will be shown on the seven segment display of the control board SDCS-CON-x as codes F . . as well as on the LCD of the control panel CDP 31x as clear text.

All fault signals - with the exception of F 17, F 18 and F 44 - can be reset (after elimination of the faults); F 20 would be self resetting, if the communication had been re-established before.

For resetting (RESET) of fault signals the following steps are re- quired:

Switching off the commands ON/OFF and RUN

Elimination of the faults

Fault acknowledgement, i.e. resetting (RESET)

a)as described for CDP 31x

or

b) by short-time setting of the command RESET

 

to high (logical one) via a binary input

 

(default setting = DI6).

Depending on the application conditions generate the commands ON/OFF and RUN once more.

The fault signals will result in switching off the signal [10910] resp. in stopping the drive (installation-dependent).

If a fault occurs, there will be three different possibilities of reaction (see column “Remark” in the fault list):

(1)Fault will switch off the signals energizing the main contactor, the field contactor and the fan contactor.

(2)Fault will switch off the signals energizing the main contactor and the field contactor.

(3)Fault will switch off at least the signal energizing the main contactor.

 

Code

 

 

Text on

 

Definition /

 

Status

 

Remark

 

seven

 

 

LCD of control panel

 

Action

 

signal

 

 

 

segm.

 

 

 

 

CDP 31x

 

 

 

(FAULT_WORD_1/2)

 

 

 

display

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F 1

 

Auxil. undervoltage

 

Auxiliary voltage fault

11101

bit 0

(1)

 

 

 

 

 

 

Try to reset. Check internal auxiliary volt-

 

 

 

 

 

 

 

 

 

 

 

ages; if fault persists, change SDCS-CON-x

 

 

 

 

 

 

 

 

 

 

 

and/ or SDCS-POW 1 board (if required).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F 2

 

Overcurrent

 

Overcurrent

11101

bit 1

(3)

 

 

 

 

 

 

Check: - Motor, load and armature cabling

 

 

 

 

 

 

 

 

 

 

 

for faults or blocking condition;

 

 

 

 

 

 

 

 

 

 

 

- Parameter setting of current con-

 

 

 

 

 

 

 

 

 

 

 

trol circuit/torque limitation;

 

 

 

 

 

 

 

 

 

 

 

- Parameter [P 512]

 

 

 

 

 

 

 

 

 

 

 

(overcurrent detection).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DCS 500B / DCP 500B Operating Instructions

IV A 4 - 3

3ADW000055R0401_DCS500B_Operating Instruction_e_d

Image 55
Contents DCS 500B / DCF 500B DCP 500B How the DCS 500 Documentation System works Operating Instructions DCS 500B / DCP 500B Operating Instructions Overview Safety InstructionsSafety Instructions Mains connection Emergency Stop buttons Intended use Contents Signals and Troubleshooting DCS 500B / DCP 500B Operating Instructions Associated publications How to use this manualContents of this manual Target groupStorage and transport Incoming inspectionRating plate = Line voltage General notesHow this chapter is structured Recommended motor voltages and field voltagesMethod of functioning of the binary inputs DI5, DI7 and DI8 System-dependent planning Symbols for enabling / disabling the referenceSymbol for measuring physical variables Symbol for displaying parameter values or connectionsPreparatory work Scaling intra-unit signals 11202 = Save MOT1 SET 518 = 500 V fixed! rated power converter voltageSet this only for units of the DCP 500 series 5191305 = Field current for Under-excitation signal Presetting the field supply unitIV a 2 1201 = 3 Panel display ARM. Autotuning Adjusting the current controllerDCS 500B / DCP 500B Operating Instructions IV a 2 Speed feedback balancing Only when the e.m.f. signal is being used as speed feedback Continue with Chapter Balancing the field supply unit and the e.m.f. controllerField weakening control with setting range 1 1204 = 1205 = If the field time constant is not known11209 = 1009 = 1010 = 1201 = 0 Panel display not Activated 11202 = Save MOT1 SET1002 = 1004 == decrease so that motor voltage is 40% 11003= decrease so that motor voltage is 70% Proceed as described in 1. / 2. / 3. above12516 = increase slowly up to 20000 =100 % speed Only if analog tacho is used as speed feedback1008 = desired response behaviour of controller 1708 = 0,1 s 1709 = 0,1 s1204 POT1 = 10%...20% max. speed 408 = desired response behaviour of controller1204 = 1205 = Presetting the 3-phase field supply unit DCF 50xB 3603 = 1201 = 5Panel display FEX2/3 Autotuning3601 = 3602 =1201 = 4Panel display ARM. MAN. Tuning ⇒ CDP ⇒ CDP 310 or CDPID-NUMBER Total 1 Drives Start ModePanel Functions ACTPAR Pin/Parameter Selecting and Changing of Value Drive ModeValue To enter the Parameter ModeBackupstoremode Saving of the Parameters to backup memoryDisplay Mode Fault Resetting ResetFault History Display DCS Uploading and Downloading of Parameters UPLOAD/DOWNLOADDCS 500B / DCP 500B Operating Instructions IV a 3 Full Name of output pins Setting of the Display ContrastDisplay Mode release key Selecting output pins Drive Mode Operational Com- mand Keys Running the DriveMode Speed Reference Setting for the DriveTo enter the Reference Setting To exit the Reference SettingDisplay of status, alarm and fault signals Signals and TroubleshootingGeneral messages Starting errors EAuxil. undervoltage Fault Signals FEarth fault Conv.fan curr.faultMotor 1 overtemp SDCS-IOB-3, SDCS-POW P418Limited by the activation of a free wheeling Circuit Ext.Overvolt.FaultLocal & discon NectedMains overvoltage Field ex.1 comerrorCheck Parameters of Field Exciter Arm. curent ripple Field ex.1 not OK See Fault Code FNo ext. FAN ack No main cont. ackIV a 4 Current Difference Reversal Fault101 Start inhibition Alarm Signals a103 Motor 1 temp. alarm Check See Fault Code F 105 Conv. overtemp120 108110 118130 127128 129138 134136 137At Macro x, macro-specific links or function 11201 Status SignalsBackupstoremode Fexcstatus 1120311205 11204DCF 500B IV a a IV a a 055R0401A2440000