Chapter 4 - Signals and Troubleshooting

 

Code

 

 

Text on

 

 

Definition /

 

Status

 

 

Remark

 

seven

 

 

LCD of control panel

 

 

Action

 

signal

 

 

 

 

segm.

 

 

 

 

 

CDP 31x

 

 

 

 

(FAULT_WORD_1/2)

 

 

 

 

display

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F 20

Local & discon-

 

 

No communication between CDP 31x/CMT

11102

bit 11

(1)

 

 

 

 

nected

 

 

and DCS 500B / DCF 500B or DCP 500B in lo-

 

 

 

 

 

Self re-

 

 

 

 

 

 

 

cal control mode (LOCAL)

 

 

 

 

 

setting

 

 

 

 

 

 

 

Check: - Connection cable between

 

 

 

 

 

 

 

 

 

 

 

 

 

CDP 31x – DCS 500 / DCP 500

 

 

 

 

 

 

 

 

 

 

 

 

 

(unplug connection cable from

 

 

 

 

 

 

 

 

 

 

 

 

 

CDP 31x and plug in again);

 

 

 

 

 

 

 

 

 

 

 

 

 

- Communication board SNAT 6xx

 

 

 

 

 

 

 

 

 

 

 

 

 

and appropriate programm O.K.?

 

 

 

 

 

 

 

 

 

 

 

 

 

- Local mode terminated when

 

 

 

 

 

 

 

 

 

 

 

 

 

panel/PC was removed?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F 21

 

 

Ext.Overvolt.Fault

 

 

Overvoltage protection DCF 506 has acted

11103

bit 12

(1)

 

 

 

 

 

 

 

There was an overvoltage condition in the

 

 

 

 

 

 

 

 

 

 

 

 

 

DC circuit of the field supply, which had been

 

 

 

 

 

S21.232

 

 

 

 

 

 

 

limited by the activation of a free wheeling

 

 

 

 

 

 

 

 

 

 

 

 

circuit.

 

 

 

 

 

and

 

 

 

 

 

 

 

 

 

 

 

 

higher

 

 

 

 

 

 

 

Check: - Power wiring of the field supply

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

- Control logic according to wiring

 

 

 

 

 

 

 

 

 

 

 

 

 

example?

 

 

 

 

 

 

 

 

 

 

 

 

 

- Does PP_DI_OVP [1216] has been

 

 

 

 

 

 

 

 

 

 

 

 

 

connected to a binary input?

 

 

 

 

 

 

 

 

 

 

 

 

 

- Setting of OVP_SELECT [1217]

 

 

 

 

 

 

 

 

 

 

 

 

 

correct? (see Alarm 121)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F 23

 

 

Motor stalled

 

 

Motor stalled

11102

bit 14

(3)

 

 

 

 

 

 

 

While starting the motor the current exceeded

 

 

 

 

 

 

 

 

 

 

 

 

 

the value of parameter [P 2207] for a time

 

 

 

 

 

 

 

 

 

 

 

 

 

longer than parameter [P 2208] and the speed

 

 

 

 

 

 

 

 

 

 

 

 

 

feedback value was below parameter [P 2206].

 

 

 

 

 

 

 

 

 

 

 

 

 

Check: - Motor stalled?

 

 

 

 

 

 

 

 

 

 

 

 

 

- Load changed during start?

 

 

 

 

 

 

 

 

 

 

 

 

 

- Correct field current?

 

 

 

 

 

 

 

 

 

 

 

 

 

- Current/torque limitation;

 

 

 

 

 

 

 

 

 

 

 

 

 

- Parameter settings [P 22xx].

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F 27

Motor 2 overload

 

 

Overload of MOTOR 2 (Thermal model 2).

11101

bit 9

(2)

 

 

 

 

 

 

 

{see Fault Code F 7}

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IV A 4 - 6

DCS 500B / DCP 500B Operating Instructions

3ADW000055R0401_DCS500B_Operating Instruction_e_d

Image 58
Contents DCS 500B / DCF 500B DCP 500B How the DCS 500 Documentation System works Operating Instructions DCS 500B / DCP 500B Operating Instructions Safety Instructions OverviewSafety Instructions Mains connection Emergency Stop buttons Intended use Contents Signals and Troubleshooting DCS 500B / DCP 500B Operating Instructions Target group How to use this manualContents of this manual Associated publicationsStorage and transport Incoming inspectionRating plate Recommended motor voltages and field voltages General notesHow this chapter is structured = Line voltageMethod of functioning of the binary inputs DI5, DI7 and DI8 Symbols for enabling / disabling the reference System-dependent planningSymbol for displaying parameter values or connections Symbol for measuring physical variablesPreparatory work Scaling intra-unit signals 519 518 = 500 V fixed! rated power converter voltageSet this only for units of the DCP 500 series 11202 = Save MOT1 SETPresetting the field supply unit 1305 = Field current for Under-excitation signalIV a 2 Adjusting the current controller 1201 = 3 Panel display ARM. AutotuningDCS 500B / DCP 500B Operating Instructions IV a 2 Speed feedback balancing Only when the e.m.f. signal is being used as speed feedback Balancing the field supply unit and the e.m.f. controller Continue with ChapterField weakening control with setting range 1 1204 = 1205 = If the field time constant is not known11209 = 1004 = 1201 = 0 Panel display not Activated 11202 = Save MOT1 SET1002 = 1009 = 1010 =Proceed as described in 1. / 2. / 3. above 11003= decrease so that motor voltage is 70% = decrease so that motor voltage is 40%Only if analog tacho is used as speed feedback 12516 = increase slowly up to 20000 =100 % speed408 = desired response behaviour of controller 1708 = 0,1 s 1709 = 0,1 s1204 POT1 = 10%...20% max. speed 1008 = desired response behaviour of controller1204 = 1205 = Presetting the 3-phase field supply unit DCF 50xB 3602 = 1201 = 5Panel display FEX2/3 Autotuning3601 = 3603 =1201 = 4Panel display ARM. MAN. Tuning ⇒ CDP 310 or CDP ⇒ CDPStart Mode ID-NUMBER Total 1 DrivesACT Panel FunctionsPAR Drive Mode Pin/Parameter Selecting and Changing of ValueTo enter the Parameter Mode ValueSaving of the Parameters to backup memory BackupstoremodeFault Resetting Reset Display ModeFault History Display Uploading and Downloading of Parameters UPLOAD/DOWNLOAD DCSDCS 500B / DCP 500B Operating Instructions IV a 3 Full Name of output pins Setting of the Display ContrastDisplay Mode release key Selecting output pins Drive Mode Running the Drive Operational Com- mand KeysTo exit the Reference Setting Speed Reference Setting for the DriveTo enter the Reference Setting ModeSignals and Troubleshooting Display of status, alarm and fault signalsStarting errors E General messagesFault Signals F Auxil. undervoltageEarth fault Conv.fan curr.faultMotor 1 overtemp P418 SDCS-IOB-3, SDCS-POWNected Ext.Overvolt.FaultLocal & discon Limited by the activation of a free wheeling CircuitMains overvoltage Field ex.1 comerrorCheck Parameters of Field Exciter Arm. curent ripple No main cont. ack See Fault Code FNo ext. FAN ack Field ex.1 not OKIV a 4 Reversal Fault Current DifferenceCheck See Fault Code F 105 Conv. overtemp Alarm Signals a103 Motor 1 temp. alarm 101 Start inhibition118 108110 120129 127128 130137 134136 138At Macro x, macro-specific links or function Status Signals 11201Backupstoremode 11203 Fexcstatus11204 11205DCF 500B IV a a IV a a 055R0401A2440000