DCS 500 manual Backupstoremode

Page 70

Chapter 4 - Signals and Troubleshooting

 

Para-

 

 

Code

 

 

Text on LCD of con-

 

 

Definition / explication of the signal

 

 

Remark

 

 

 

 

/

 

 

 

 

 

 

 

 

meter

 

 

 

 

trol panel CDP 31x

 

 

 

 

 

 

 

 

 

 

bit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

11201

--

----

 

 

Gives feedback status information when the

 

 

 

 

 

 

 

 

 

 

 

 

 

DRIVEMODE parameter (1201) was used to start the

 

 

 

 

 

 

 

 

 

 

 

 

 

drive function 3, 5 or 6 (autotuning).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

50

OHMIC LOAD ?

 

Ohmic load not determined

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

51

IACT FEEDBACK ?

 

Current feedback is less than current reference dur-

 

 

 

 

 

 

 

 

 

 

 

 

 

ing measurement of armature resistance. Current

 

 

 

 

 

 

 

 

 

 

 

 

 

limits are lower than the limit for continous current

 

 

 

 

 

 

 

 

 

 

 

 

 

flow or lower than 20%.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

52

CURRENT CURVE ?

 

Bad current curve. Fuse blown,thyristor not firing or

 

 

 

 

 

 

 

 

 

 

 

 

 

no motor load

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

53

RUN COMMAND ?

 

Wrong starting conditions. The drive is running when

 

 

 

 

 

 

 

 

 

 

 

 

 

the autotuning is started or run command is not given

 

 

 

 

 

 

 

 

 

 

 

 

 

within 20 s after start of autotuning

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

54

TOO HIGH SPEED ?

 

Too high speed during autotuning .Speed greater

 

 

 

 

 

 

 

 

 

 

 

 

 

than 1% or EMF greater than 15%.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

55

INDUCTANCE ?

 

Inductance cannot be determined. Fuse blown, thy-

 

 

 

 

 

 

 

 

 

 

 

 

 

ristor not firing or no motor load

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

56

CONT CURR LIM ?

 

Limit for continous current flow cannot be determined

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

57

FIELD REMOVAL ?

 

The field removal takes longer time than 10 s

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

58

STOP COMMAND ?

 

Current regulator blocking or stop command appears

 

 

 

 

 

 

 

 

 

 

 

 

 

during autotuning

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

59

MUST BE LOCAL

 

Drive is not in local mode

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

60

CANNOT AUTOTUNE

 

cannot autotune the field current controller

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

61

ILL START COND.

 

illegal start condition for field autotuning

 

 

 

 

 

 

 

 

 

 

 

 

 

11202

--

----

 

BACKUPSTOREMODE:

 

 

 

 

 

 

 

 

 

 

 

 

 

Status of this mode. This is used to give commands

 

 

 

 

 

 

 

 

 

 

 

 

 

to parameter handling function in the drive

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0

NONE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

SAVE MOT1 SET

 

Save motor set 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

SAVE MOT2 SET

 

Save motor set 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

FACTORY SET VAL.

 

Load factory values

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

SELECT MOT1 SET

 

Load motor set 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

SELECT MOT2 SET

 

Load motor set 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IV A 4 - 18

DCS 500B / DCP 500B Operating Instructions

3ADW000055R0401_DCS500B_Operating Instruction_e_d

Image 70
Contents DCS 500B / DCF 500B DCP 500B How the DCS 500 Documentation System works Operating Instructions DCS 500B / DCP 500B Operating Instructions Safety Instructions OverviewSafety Instructions Mains connection Emergency Stop buttons Intended use Contents Signals and Troubleshooting DCS 500B / DCP 500B Operating Instructions Target group How to use this manualContents of this manual Associated publicationsStorage and transport Incoming inspectionRating plate Recommended motor voltages and field voltages General notesHow this chapter is structured = Line voltageMethod of functioning of the binary inputs DI5, DI7 and DI8 Symbols for enabling / disabling the reference System-dependent planningSymbol for displaying parameter values or connections Symbol for measuring physical variablesPreparatory work Scaling intra-unit signals 519 518 = 500 V fixed! rated power converter voltageSet this only for units of the DCP 500 series 11202 = Save MOT1 SETPresetting the field supply unit 1305 = Field current for Under-excitation signalIV a 2 Adjusting the current controller 1201 = 3 Panel display ARM. AutotuningDCS 500B / DCP 500B Operating Instructions IV a 2 Speed feedback balancing Only when the e.m.f. signal is being used as speed feedback Balancing the field supply unit and the e.m.f. controller Continue with ChapterField weakening control with setting range 1 1204 = 1205 = If the field time constant is not known11209 = 1004 = 1201 = 0 Panel display not Activated 11202 = Save MOT1 SET1002 = 1009 = 1010 =Proceed as described in 1. / 2. / 3. above 11003= decrease so that motor voltage is 70% = decrease so that motor voltage is 40%Only if analog tacho is used as speed feedback 12516 = increase slowly up to 20000 =100 % speed408 = desired response behaviour of controller 1708 = 0,1 s 1709 = 0,1 s1204 POT1 = 10%...20% max. speed 1008 = desired response behaviour of controller1204 = 1205 = Presetting the 3-phase field supply unit DCF 50xB 3602 = 1201 = 5Panel display FEX2/3 Autotuning3601 = 3603 =1201 = 4Panel display ARM. MAN. Tuning ⇒ CDP 310 or CDP ⇒ CDPStart Mode ID-NUMBER Total 1 DrivesACT Panel FunctionsPAR Drive Mode Pin/Parameter Selecting and Changing of ValueTo enter the Parameter Mode ValueSaving of the Parameters to backup memory BackupstoremodeFault Resetting Reset Display ModeFault History Display Uploading and Downloading of Parameters UPLOAD/DOWNLOAD DCSDCS 500B / DCP 500B Operating Instructions IV a 3 Full Name of output pins Setting of the Display ContrastDisplay Mode release key Selecting output pins Drive Mode Running the Drive Operational Com- mand KeysTo exit the Reference Setting Speed Reference Setting for the DriveTo enter the Reference Setting ModeSignals and Troubleshooting Display of status, alarm and fault signalsStarting errors E General messagesFault Signals F Auxil. undervoltageEarth fault Conv.fan curr.faultMotor 1 overtemp P418 SDCS-IOB-3, SDCS-POWNected Ext.Overvolt.FaultLocal & discon Limited by the activation of a free wheeling CircuitMains overvoltage Field ex.1 comerrorCheck Parameters of Field Exciter Arm. curent ripple No main cont. ack See Fault Code FNo ext. FAN ack Field ex.1 not OKIV a 4 Reversal Fault Current DifferenceCheck See Fault Code F 105 Conv. overtemp Alarm Signals a103 Motor 1 temp. alarm 101 Start inhibition118 108110 120129 127128 130137 134136 138At Macro x, macro-specific links or function Status Signals 11201Backupstoremode 11203 Fexcstatus11204 11205DCF 500B IV a a IV a a 055R0401A2440000