DCS 500 manual Arm. curent ripple

Page 60

Chapter 4 - Signals and Troubleshooting

 

Code

 

 

Text on

 

 

Definition /

 

 

Status

 

 

Remark

 

seven

 

 

LCD of control panel

 

 

Action

 

 

signal

 

 

 

 

segm.

 

 

 

 

 

 

 

CDP 31x

 

 

 

 

 

(FAULT_WORD_1/2)

 

 

 

 

display

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F 34

Arm. curent ripple

 

Armature current ripple

 

11102

bit 0

(3)

 

 

 

 

 

 

One or several thyristors carry no current.

 

 

 

 

 

 

 

 

 

 

 

 

 

Check: - Current feedback with oscilloscope

 

 

 

 

 

 

modified

 

 

 

 

 

 

 

(6 pulses within one cycle visible?)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

in

 

 

 

 

 

 

 

- Branch fuses, thyristor gate con

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S21.232

 

 

 

 

 

 

 

nection; gate-cathode resistance.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

- Sensitivity of monitoring function:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

set CUR_RIPPLE_LIM [421] (de

 

 

 

 

 

 

 

 

 

 

 

 

 

 

pending on methode; see A 137)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F 35

Field ex.2 overcurr

 

FIELD EXCITER 2 (field supply 2) overcurrent

 

11102

bit 1

(1)

 

 

 

 

 

 

{See Fault Code F 32}

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F 36

Field ex.2 comerror

 

FIELD EXCITER 2 communication error

 

11102

bit 2

(1)

 

 

 

 

 

 

{See Fault Code F 33}

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F 37

 

 

Motor overspeed

 

Motor overspeed

 

11102

bit 15

(3)

 

 

 

 

 

 

Speed feedback higher than parameter

 

 

 

 

 

 

 

 

 

 

 

 

 

[P 2204].

 

 

 

 

 

 

 

 

 

 

 

 

 

Check: - Scaling of speed controller loop;

 

 

 

 

 

 

 

 

 

 

 

 

 

 

- Drive speed;

 

 

 

 

 

 

 

 

 

 

 

 

 

 

- Field refererence values;

 

 

 

 

 

 

 

 

 

 

 

 

 

 

- Speed feedback and connection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

of speed feedback;

 

 

 

 

 

 

 

 

 

 

 

 

 

 

- Was the motor accelerated by

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the load?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F 38

 

 

Phase sequence

 

Phase sequence fault of power section

 

11102

bit 3

(3)

 

 

 

 

fault

 

Change supply phase sequency or make

 

 

 

 

 

 

 

 

 

 

 

 

 

correction with parameter [P 506].

 

 

 

 

 

 

 

 

 

 

 

 

 

Attention: Direction of rotation of 3-phase

 

 

 

 

 

 

 

 

 

 

 

 

 

 

fan correct?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F 39

No field ack.

 

No field acknowledge from FIELD EXCITER

 

11102

bit 4

(1)

 

 

 

 

 

 

This message is either caused by the field exciter´s

 

 

 

 

 

 

 

 

 

 

 

 

 

missing „ready for operation“ signal (1) or the field

 

 

 

 

 

 

 

 

 

 

 

 

 

current being lower than the threshold (2). Reasons

 

 

 

 

 

 

 

 

 

 

 

 

 

for (1):

 

 

 

 

 

 

 

 

 

 

 

 

 

-

field supply not in synchronism, or

 

 

 

 

 

 

 

 

 

 

 

 

 

-

electronic power supply for the field unit not within

 

 

 

 

 

 

 

 

 

 

 

 

 

-

permissible limits

 

 

 

 

 

 

 

 

 

 

 

 

 

power supply for the field unit not within permissi-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ble limits

 

 

 

 

 

 

 

 

 

 

 

 

 

Reasons for (2):

 

 

 

 

 

 

 

 

 

 

 

 

 

-

field supply unit is broken

 

 

 

 

 

 

 

 

 

 

 

 

 

-

field reversal took too long time

 

 

 

 

 

 

 

 

 

 

 

 

 

-

field current lower than threshold because

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IV A 4 - 8

DCS 500B / DCP 500B Operating Instructions

3ADW000055R0401_DCS500B_Operating Instruction_e_d

Image 60
Contents DCS 500B / DCF 500B DCP 500B How the DCS 500 Documentation System works Operating Instructions DCS 500B / DCP 500B Operating Instructions Safety Instructions OverviewSafety Instructions Mains connection Emergency Stop buttons Intended use Contents Signals and Troubleshooting DCS 500B / DCP 500B Operating Instructions How to use this manual Contents of this manualTarget group Associated publicationsIncoming inspection Storage and transportRating plate General notes How this chapter is structuredRecommended motor voltages and field voltages = Line voltageMethod of functioning of the binary inputs DI5, DI7 and DI8 Symbols for enabling / disabling the reference System-dependent planningSymbol for displaying parameter values or connections Symbol for measuring physical variablesPreparatory work Scaling intra-unit signals 518 = 500 V fixed! rated power converter voltage Set this only for units of the DCP 500 series519 11202 = Save MOT1 SETPresetting the field supply unit 1305 = Field current for Under-excitation signalIV a 2 Adjusting the current controller 1201 = 3 Panel display ARM. AutotuningDCS 500B / DCP 500B Operating Instructions IV a 2 Speed feedback balancing Only when the e.m.f. signal is being used as speed feedback Balancing the field supply unit and the e.m.f. controller Continue with ChapterField weakening control with setting range 1 If the field time constant is not known 1204 = 1205 =11209 = 1201 = 0 Panel display not Activated 11202 = Save MOT1 SET 1002 =1004 = 1009 = 1010 =11003 = decrease so that motor voltage is 70%Proceed as described in 1. / 2. / 3. above = decrease so that motor voltage is 40%Only if analog tacho is used as speed feedback 12516 = increase slowly up to 20000 =100 % speed1708 = 0,1 s 1709 = 0,1 s 1204 POT1 = 10%...20% max. speed408 = desired response behaviour of controller 1008 = desired response behaviour of controller1204 = 1205 = Presetting the 3-phase field supply unit DCF 50xB 1201 = 5Panel display FEX2/3 Autotuning 3601 =3602 = 3603 =1201 = 4Panel display ARM. MAN. Tuning ⇒ CDP 310 or CDP ⇒ CDPStart Mode ID-NUMBER Total 1 DrivesACT Panel FunctionsPAR Drive Mode Pin/Parameter Selecting and Changing of ValueTo enter the Parameter Mode ValueSaving of the Parameters to backup memory BackupstoremodeFault Resetting Reset Display ModeFault History Display Uploading and Downloading of Parameters UPLOAD/DOWNLOAD DCSDCS 500B / DCP 500B Operating Instructions IV a 3 Setting of the Display Contrast Full Name of output pinsDisplay Mode release key Selecting output pins Drive Mode Running the Drive Operational Com- mand KeysSpeed Reference Setting for the Drive To enter the Reference SettingTo exit the Reference Setting ModeSignals and Troubleshooting Display of status, alarm and fault signalsStarting errors E General messagesFault Signals F Auxil. undervoltageConv.fan curr.fault Earth faultMotor 1 overtemp P418 SDCS-IOB-3, SDCS-POWExt.Overvolt.Fault Local & disconNected Limited by the activation of a free wheeling CircuitField ex.1 comerror Mains overvoltageCheck Parameters of Field Exciter Arm. curent ripple See Fault Code F No ext. FAN ackNo main cont. ack Field ex.1 not OKIV a 4 Reversal Fault Current DifferenceAlarm Signals a 103 Motor 1 temp. alarmCheck See Fault Code F 105 Conv. overtemp 101 Start inhibition108 110118 120127 128129 130134 136137 138At Macro x, macro-specific links or function Status Signals 11201Backupstoremode 11203 Fexcstatus11204 11205DCF 500B IV a a IV a a 055R0401A2440000