DCS 500 manual Conv.fan curr.fault, Earth fault, Motor 1 overtemp

Page 56

Chapter 4 - Signals and Troubleshooting

Code

Text on

Definition /

Status

Remark

seven

LCD of control panel

Action

signal

 

segm.

CDP 31x

 

(FAULT_WORD_1/2)

 

display

 

 

 

 

 

 

F 3

Conv.fan curr.fault

Current converter fan not within limits

11103 bit 11

(1)

The current of the converter´s cooling fan is

 

measured via the option board PW1002/3.

S21.232

Check: - Fan supply, fan current;

- Setting of PW1002,

and

higher

SET_MAX_BR_TEMP [P519] and

 

CONV_TEMP_DELAY [P527]

 

-Direction of rotation, fan compo nents, air inlet

F 4 Converter overtemp. Overtemperature power section

11101 bit 3

(2)

Check: - Fan supply, direction of rotation, fan components, air inlet and ambient temperature;

- Inadmissible load cycle?

F 5

Earth fault

Earth fault (Σ I differs from zero)

11101 bit 4

(1)

Disconnect the mains and verify zero voltage in armature and field circuits.

Make insulation test for the complete installation.

Check sum current transformer; if necessary, change transformer and SDCS-IOB-3 board.

F 6 Motor 1 overtemp.

Overtemperature of MOTOR 1

11101 bit 5 (2)

Check: - Temperature sensor and its cabling;

-Motor cooling or sizing;

-Inputs for temperature sensor on board SDCS-IOB-3;

-Parameter setting MOT1.TEMP_

FAULT_L [P 1403] correct?

Note: It will only be possible to reset this fault signal when the motor temperature has fallen below the threshold which is valid for the alarm signal A 103; the signal will also be evaluated while the mains contactor is de-energized (open).

F 7 Motor 1 overload

Overload of MOTOR 1 (Thermal model 1)

11101 bit 6

(2)

 

Check: - Motor temperature (let motor cool

 

 

 

down and restart);

 

 

-Motor ratings and parameters of thermal model;

-Motor sizing or load cycle.

IV A 4 - 4

DCS 500B / DCP 500B Operating Instructions

3ADW000055R0401_DCS500B_Operating Instruction_e_d

Image 56
Contents DCS 500B / DCF 500B DCP 500B How the DCS 500 Documentation System works Operating Instructions DCS 500B / DCP 500B Operating Instructions Safety Instructions OverviewSafety Instructions Mains connection Emergency Stop buttons Intended use Contents Signals and Troubleshooting DCS 500B / DCP 500B Operating Instructions How to use this manual Contents of this manualTarget group Associated publicationsRating plate Incoming inspectionStorage and transport General notes How this chapter is structuredRecommended motor voltages and field voltages = Line voltageMethod of functioning of the binary inputs DI5, DI7 and DI8 Symbols for enabling / disabling the reference System-dependent planningSymbol for displaying parameter values or connections Symbol for measuring physical variablesPreparatory work Scaling intra-unit signals 518 = 500 V fixed! rated power converter voltage Set this only for units of the DCP 500 series519 11202 = Save MOT1 SETPresetting the field supply unit 1305 = Field current for Under-excitation signalIV a 2 Adjusting the current controller 1201 = 3 Panel display ARM. AutotuningDCS 500B / DCP 500B Operating Instructions IV a 2 Speed feedback balancing Only when the e.m.f. signal is being used as speed feedback Balancing the field supply unit and the e.m.f. controller Continue with ChapterField weakening control with setting range 1 11209 = If the field time constant is not known1204 = 1205 = 1201 = 0 Panel display not Activated 11202 = Save MOT1 SET 1002 =1004 = 1009 = 1010 =11003 = decrease so that motor voltage is 70%Proceed as described in 1. / 2. / 3. above = decrease so that motor voltage is 40%Only if analog tacho is used as speed feedback 12516 = increase slowly up to 20000 =100 % speed1708 = 0,1 s 1709 = 0,1 s 1204 POT1 = 10%...20% max. speed408 = desired response behaviour of controller 1008 = desired response behaviour of controller1204 = 1205 = Presetting the 3-phase field supply unit DCF 50xB 1201 = 5Panel display FEX2/3 Autotuning 3601 =3602 = 3603 =1201 = 4Panel display ARM. MAN. Tuning ⇒ CDP 310 or CDP ⇒ CDPStart Mode ID-NUMBER Total 1 DrivesACT Panel FunctionsPAR Drive Mode Pin/Parameter Selecting and Changing of ValueTo enter the Parameter Mode ValueSaving of the Parameters to backup memory BackupstoremodeFault Resetting Reset Display ModeFault History Display Uploading and Downloading of Parameters UPLOAD/DOWNLOAD DCSDCS 500B / DCP 500B Operating Instructions IV a 3 Display Mode release key Setting of the Display ContrastFull Name of output pins Selecting output pins Drive Mode Running the Drive Operational Com- mand KeysSpeed Reference Setting for the Drive To enter the Reference SettingTo exit the Reference Setting ModeSignals and Troubleshooting Display of status, alarm and fault signalsStarting errors E General messagesFault Signals F Auxil. undervoltageMotor 1 overtemp Conv.fan curr.faultEarth fault P418 SDCS-IOB-3, SDCS-POWExt.Overvolt.Fault Local & disconNected Limited by the activation of a free wheeling CircuitCheck Parameters of Field Exciter Field ex.1 comerrorMains overvoltage Arm. curent ripple See Fault Code F No ext. FAN ackNo main cont. ack Field ex.1 not OKIV a 4 Reversal Fault Current DifferenceAlarm Signals a 103 Motor 1 temp. alarmCheck See Fault Code F 105 Conv. overtemp 101 Start inhibition108 110118 120127 128129 130134 136137 138At Macro x, macro-specific links or function Status Signals 11201Backupstoremode 11203 Fexcstatus11204 11205DCF 500B IV a a IV a a 055R0401A2440000