Chapter 4 - Signals and Troubleshooting

 

Code

 

 

Text on

 

 

Definition /

 

Status

 

 

Remark

 

seven

 

 

LCD of control panel

 

 

Action

 

signal

 

 

 

 

segm.

 

 

 

 

 

 

 

CDP 31x

 

 

 

 

(FAULT_WORD_1/2)

 

 

 

 

display

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F 8

 

Current rise fault

 

Actual current changed faster than allowed

11103

bit 10

(2)

 

 

 

 

 

 

The rate of current change is monitored.

 

 

 

 

 

 

 

 

 

 

 

 

Check: - Setting of current reference slope

 

 

 

 

 

S21.232

 

 

 

 

 

 

 

[P406] and CURRENT_RISE_MAX

 

 

 

 

 

 

 

 

 

 

 

 

[P418];

 

 

 

 

 

and

 

 

 

 

 

 

 

 

 

 

 

 

higher

 

 

 

 

 

 

 

Level and setting of line voltage

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

and motor voltage; setting of

 

 

 

 

 

 

 

 

 

 

 

 

 

current controler

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F 14

 

Speed meas. fault

 

Speed feedback (measurement) fault

11102

bit 5

(3)

 

 

 

 

 

 

Check: - Incremental encoder and connec-

 

 

 

 

 

 

 

 

 

 

 

 

 

tion cable, encoder power supply

 

 

 

 

 

 

 

 

 

 

 

 

 

(feedback might be too low);

 

 

 

 

 

 

 

 

 

 

 

 

 

- Tacho polarity and voltage

 

 

 

 

 

 

 

 

 

 

 

 

 

(does a total mismatch exist?)

 

 

 

 

 

 

 

 

 

 

 

 

 

- Electronic boards SDCS-CON-x,

 

 

 

 

 

 

 

 

 

 

 

 

 

SDCS-IOB-3, SDCS-POW 1;

 

 

 

 

 

 

 

 

 

 

 

 

 

- Connection converter – armature

 

 

 

 

 

 

 

 

 

 

 

 

 

circuit open?

 

 

 

 

 

 

 

 

 

 

 

 

 

- Correct setting for selection of

 

 

 

 

 

 

 

 

 

 

 

 

 

speed feedback monitoring?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F 17

 

Type coding fault

 

(Converter) Type coding fault

11102

bit 8

(1)

 

 

 

 

 

 

SDCS-PIN-xx board not connected to board

 

 

 

 

 

Can

 

 

 

 

 

 

SDCS-CON-x or SDCS-PIN-xx not coded.

 

 

 

 

 

not be

 

 

 

 

 

 

Check: - Flat cables X12 and X13 O.K.?

 

 

 

 

 

reset

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

- Faulty coding on SDCS-PIN-xx?

 

 

 

 

 

 

 

 

 

 

 

 

 

- Correct coding of unit size C4?

 

 

 

 

 

 

 

 

 

 

 

 

Note: This fault signal will be shown, if jumper S2 (on board

 

 

 

 

 

 

 

 

 

 

 

 

SDCS-CON-x) is in position 1–2 while switching ON the elec-

 

 

 

 

 

 

 

 

 

 

 

 

tronics supply. In that case select BACKUP-STOREMODE

 

 

 

 

 

 

 

 

 

 

 

 

[11202], save the paramter set, switch OFF the electronics,

 

 

 

 

 

 

 

 

 

 

 

 

reset jumper S2 and switch ON the electronics again.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

F 18

 

Backup read fault

 

Backup read fault (Parameter saving fault)

11102

bit 9

(1)

 

 

 

 

 

 

Cause: Wrong or missing checksum, data error

 

 

 

 

 

Can

 

 

 

 

 

 

while writing or reading.

 

 

 

 

 

not be

 

 

 

 

 

 

Note: Try again BACKUP-STORE-MODE; for that purpose

 

 

 

 

 

reset

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

- Move jumper S2 (on board SDCS-CON-x) to Pos. 1–2

 

 

 

 

 

 

 

 

 

 

 

 

 

with electronics supply switched OFF;

 

 

 

 

 

 

 

 

 

 

 

 

-

Switch ON electronics again;

 

 

 

 

 

 

 

 

 

 

 

 

- Select BACKUPSTOREMODE [11202];

 

 

 

 

 

 

 

 

 

 

 

 

-

Save default parameter set;

 

 

 

 

 

 

 

 

 

 

 

 

-

Switch OFF electronics;

 

 

 

 

 

 

 

 

 

 

 

 

-

Reset jumper S2 to ist original position;

 

 

 

 

 

 

 

 

 

 

 

 

-

Switch ON electronics again.

 

 

 

 

 

 

 

 

 

 

 

 

If display shows F 18 once again, change SDCS-CON-x

 

 

 

 

 

 

 

 

 

 

 

 

board!

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DCS 500B / DCP 500B Operating Instructions

IV A 4 - 5

3ADW000055R0401_DCS500B_Operating Instruction_e_d

Image 57
Contents DCS 500B / DCF 500B DCP 500B How the DCS 500 Documentation System works Operating Instructions DCS 500B / DCP 500B Operating Instructions Overview Safety InstructionsSafety Instructions Mains connection Emergency Stop buttons Intended use Contents Signals and Troubleshooting DCS 500B / DCP 500B Operating Instructions Contents of this manual How to use this manualTarget group Associated publicationsIncoming inspection Storage and transportRating plate How this chapter is structured General notesRecommended motor voltages and field voltages = Line voltageMethod of functioning of the binary inputs DI5, DI7 and DI8 System-dependent planning Symbols for enabling / disabling the referenceSymbol for measuring physical variables Symbol for displaying parameter values or connectionsPreparatory work Scaling intra-unit signals Set this only for units of the DCP 500 series 518 = 500 V fixed! rated power converter voltage519 11202 = Save MOT1 SET1305 = Field current for Under-excitation signal Presetting the field supply unitIV a 2 1201 = 3 Panel display ARM. Autotuning Adjusting the current controllerDCS 500B / DCP 500B Operating Instructions IV a 2 Speed feedback balancing Only when the e.m.f. signal is being used as speed feedback Continue with Chapter Balancing the field supply unit and the e.m.f. controllerField weakening control with setting range 1 If the field time constant is not known 1204 = 1205 =11209 = 1002 = 1201 = 0 Panel display not Activated 11202 = Save MOT1 SET1004 = 1009 = 1010 == decrease so that motor voltage is 70% 11003Proceed as described in 1. / 2. / 3. above = decrease so that motor voltage is 40%12516 = increase slowly up to 20000 =100 % speed Only if analog tacho is used as speed feedback1204 POT1 = 10%...20% max. speed 1708 = 0,1 s 1709 = 0,1 s408 = desired response behaviour of controller 1008 = desired response behaviour of controller1204 = 1205 = Presetting the 3-phase field supply unit DCF 50xB 3601 = 1201 = 5Panel display FEX2/3 Autotuning3602 = 3603 =1201 = 4Panel display ARM. MAN. Tuning ⇒ CDP ⇒ CDP 310 or CDPID-NUMBER Total 1 Drives Start ModePanel Functions ACTPAR Pin/Parameter Selecting and Changing of Value Drive ModeValue To enter the Parameter ModeBackupstoremode Saving of the Parameters to backup memoryDisplay Mode Fault Resetting ResetFault History Display DCS Uploading and Downloading of Parameters UPLOAD/DOWNLOADDCS 500B / DCP 500B Operating Instructions IV a 3 Setting of the Display Contrast Full Name of output pinsDisplay Mode release key Selecting output pins Drive Mode Operational Com- mand Keys Running the DriveTo enter the Reference Setting Speed Reference Setting for the DriveTo exit the Reference Setting ModeDisplay of status, alarm and fault signals Signals and TroubleshootingGeneral messages Starting errors EAuxil. undervoltage Fault Signals FConv.fan curr.fault Earth faultMotor 1 overtemp SDCS-IOB-3, SDCS-POW P418Local & discon Ext.Overvolt.FaultNected Limited by the activation of a free wheeling CircuitField ex.1 comerror Mains overvoltageCheck Parameters of Field Exciter Arm. curent ripple No ext. FAN ack See Fault Code FNo main cont. ack Field ex.1 not OKIV a 4 Current Difference Reversal Fault103 Motor 1 temp. alarm Alarm Signals aCheck See Fault Code F 105 Conv. overtemp 101 Start inhibition110 108118 120128 127129 130136 134137 138At Macro x, macro-specific links or function 11201 Status SignalsBackupstoremode Fexcstatus 1120311205 11204DCF 500B IV a a IV a a 055R0401A2440000