Panasonic R410A Service procedures, Details of Alarm Messages, Alarm “P29”, MDC trouble

Models: R410A

1 198
Download 198 pages 33.93 Kb
Page 172
Image 172
(1) [Alarm “P29”]

4. Service procedures

4-3. Details of Alarm Messages

(1) [Alarm “P29”]

Input power detection circuit trouble

(MDC trouble)

Compressor does not run.

 

 

Breakdown

 

Motor current detection circuit trouble

 

Is power OK?

No

Correct power line.

 

 

 

Yes

 

 

 

 

Is

 

 

 

 

current

No

Check and correct

 

detection

 

circuit wiring

 

wiring.

 

 

OK?

 

 

 

 

Are

 

 

 

 

wiring and

No

Check and correct

 

connector

 

 

wiring.

 

 

connections

 

 

 

 

 

 

 

OK?

 

 

 

 

Yes

 

 

 

 

Is

No

 

 

 

compressor

 

 

 

 

 

 

 

OK?

 

 

Yes

 

 

 

Ground

 

 

 

 

 

Yes

 

fault?

 

 

 

 

 

 

 

 

Coil

Yes

 

 

 

resistor

 

 

 

short circuit?

 

 

 

 

Coil open

Yes

 

 

 

 

 

 

 

circuit?

 

 

 

 

No

 

 

Is there

No

Replace

 

 

 

 

abnormal refrigerant

 

4

 

compressor.

accumulation?

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

Is

 

Are

 

 

 

 

 

operation of

No

No

 

C1 and TS

 

electronic

 

 

sensors

 

 

control valve

 

 

 

 

OK?

 

 

OK?

 

 

 

 

 

 

 

Yes

 

Replace electronic

 

 

 

 

 

 

control valve.

 

Is there overload?

No

Remove

 

 

 

the cause.

 

 

 

 

 

Yes

Replace outdoor unit control PCB.

Replace compressor.

Replace C1 and TS sensors.