6-25. Checking the Drainage

CAUTION

Be careful since the fan will start Do not install an air bleeder tube as this may cause water to spray from the drain pipe outlet. (Fig. 1-76)

when you short the pin on the If it is necessary to increase the height of the drain pipe, the section directly after the connection port can be raised a maximum of 19-11/16".

Do not raise it any higher than 19-11/16", as this could result in water leaks. (Fig. 1-77)

indoor control board. Do not install the pipe with an upward gradient from the connection port. This will cause the drain water to flow backward and leak when the unit is not operating. (Fig. 1-78)

To mount the tube cover, use 5/16" Do not apply force to the piping on the unit side when connecting the drain pipe. The pipe should not be allowed to hang unsupported from its connection

1 to the unit. Fasten the pipe to a wall, frame, or other support as close to the unit as possible. (Fig. 1-79)

Refer to “ (4 × 8 mm) tapping screws. SUPPLEMENT ON DRAIN PIPING”.

6-25. Checking the Drainage

After wiring and drain piping are completed, use the following procedure to check that the water will drain smoothly. For this, prepare a bucket and wiping cloth to catch and wipe up spilled water.

(1)Connect power to the power terminal board (L1, L2 terminal) inside the electrical component box.

(2)Remove the tube cover and through the opening, slowly pour about 0.3 gal. of water into the drain pan to check drainage.

(3)Short the check pin (CN5 white) on the indoor control board and operate the drain pump. Check the water

CAUTION

Be careful since the fan will start

when you short the pin on the

 

 

 

indoor control board.

(4)When the check of drainage is complete, open the check pin (CN5 white) and remount the insulator and drain cap onto the drain inspection port.

CAUTION

To mount the tube cover, use 5/16"

(4 × 8 mm) tapping screws.

 

 

 

Do not use long screws as they

 

may puncture the drain pan and

1. Specifications

Air bleeder

Not good

Fig. 1-76

Do not use long screws as theymay puncture the drain pan and 11-13/16" or less

19-11/16" or less

Good

Fig. 1-77

Upward gradient

No good

Fig. 1-78

Support pieces

Good

Fig. 1-79

1-96