Panasonic R410A service manual Service procedures, Alarm “P26”, HIC PCB trouble

Models: R410A

1 198
Download 198 pages 33.93 Kb
Page 173
Image 173
(2) [Alarm “P26”]

4. Service procedures

(2) [Alarm “P26”]

IGBT short-circuit protection on inverter control (IPDU) PCB

HIC PCB trouble)

 

Is power OK?

No

Correct power line.

Yes

 

Are

 

circuit wiring,

 

connector

No

connections, and

Correct.

reactor

 

connections

 

OK?

 

Yes

 

Has filter PCB

No

RY001 or RY002

 

relay activated?

 

Yes

Disconnect U.V.W. output

terminal on HIC PCB and No start operation.

Does alarm

“P26”

occur?

Yes

Is

compressor OK? No (Check for layer

short circuit.)

Yes

Is

resistance between

each terminal on No

HIC PCB OK? (See following page.)

Yes

Replace outdoor unit control PCB.

Has filter PCB

Yes

Replace filter PCB.

AC fuse blown?

 

 

 

No

Replace HIC PCB.

4

Replace compressor.

Check HIC PCB. Replace if PCB has failed.

4-9

Page 173
Image 173