Check Pin

4. Service procedures

Check Pin

Short-circuit the cooling check pin (or heating check pin) on the outdoor unit control PCB to perform the control described below.

1.Thermistor checks

The checks listed below are performed for 1 second each, in order from the top down. The results are displayed by LED 1 and 2.

Thermistor

 

Check results

 

 

 

Normal

 

Abnormal

 

 

 

 

 

 

Discharge temp. (TD)

LED 1 lit

 

 

 

 

 

 

Outdoor air temp. (TO)

LED 2 lit

 

 

 

 

 

 

Heat exchanger temp. (C1)

LED 1 lit

 

LED 1 and 2 OFF

 

 

 

 

Heat exchanger temp. (C2)

 

 

 

 

 

 

 

Intake temp. (TS)

LED 1 lit

 

 

2.4-way valve turns ON for 1 second.

3.Forced cooling (or heating) operation

4-4. Table of Thermistor Characteristics

(1) Outdoor Air Temp. (TO), Intake Temp. (TS), Heat

(2) Discharge Temp. (TD) Sensors

Exchanger Temp. (C1) Sensor, Heat Exchanger

 

Temp. (C2) Sensor

 

Resistance (k)

Resistance (k)

4

Temperature (˚F)

Temperature (°F)