Outdoor Unit

1-12. Installation Instructions

Outdoor Unit

1. Tubing Size

Single type

Table 1-1 Refrigerant tubing between the indoor and outdoor units should be kept as short as possible.

Indoor unit type The length of the refrigerant tubes between the indoor and outdoor units are limited by the elevation difference between the 2 units. During tubing work, try to make both the tubing length (L) and the difference in elevation (H1) as short as possible. Refer to Table 1-2.

Table 1-1

Indoor unit type

26, 36 types

1. Specifications

Single

Main tubing L

H1

 

42 type

Maximum length

165 ft.

165 ft.

Charge-less tubing length (actual length)

10 – 100 ft.

15 – 100 ft.

Additional charge per 1 ft.

0.43 oz.

1

Maximum indoor-outdoor height difference

If outdoor unit is higher

H1

 

 

 

100

 

 

If outdoor unit is lower

H1

 

 

50

 

 

 

 

 

 

 

 

Table 1-2 Tubing Data for Models

Tubing Data

 

Models

U-26PE1U6

U-36PE1U6

U-42PE1U6

 

 

U-26PS1U6

U-36PS1U6

U-42PS1U6

Tubing size

Liquid tube

in. (mm)

3/8 (9.52)

3/8 (9.52)

3/8 (9.52)

outer diameter

Gas tube

in. (mm)

5/8 (15.88)

5/8 (15.88)

5/8 (15.88)

Limit of tubing length

 

(ft.)

165

165

165

Limit of elevation

Outdoor unit is placed

100

100

100

higher.

(ft.)

 

 

 

difference between

 

 

 

Outdoor unit is placed

 

 

 

the 2 units

50

50

50

lower.

(ft.)

 

 

 

 

 

Max. allowable tubing length at shipment

(ft.)

10 – 100

10 – 100

10 – 100

Required additional refrigerant * 1

(oz./ft.)

a) 0.43

b) 0.43

b) 0.43

Refrigerant charged at shipment

(lbs.)

4.2

6.2

7.9

No additional charge of compressor oil is necessary.

*1 If total tubing length becomes 100 to 165 ft., charge additional refrigerant by 0.43 oz./ft.

Table 1-3 List of Connection Tube Sizes

 

Main tubing (L)

 

 

Type capacity of indoor units

26 – 42

Gas tube

ø5/8"

 

 

Liquid tube

ø3/8"

Amount of additional charge per 1 ft.

0.43 oz.

1-63

Page 69