Image 195
Fig. 6-6a

6. Test run

Basic wiring diagram 2

Group control (when a central control device is not used)

Simultaneous-operation multi system

A maximum of 8 indoor units can be connected to 1 remote controller.

Set the system address (refrigerant tubing system address) before turning on the remote power switch. (Refer to “Setting the system addresses” on next page.)

(Set using the system address rotary switch on the outdoor unit control PCB.)

1

System address rotary switch (Set to “0” at the time of shipment.)

2

System address rotary switch

(Set to “0” at the time of shipment.)

Power supply Single-phase 230 / 208 V

Outdoor unit

 

 

L1 L2

1

2

G U1 U2

powerline

60V,Hz

 

 

Ground

 

 

 

Inter-unit

230 / 208

 

 

1

 

 

 

2

 

 

 

Indoor

 

 

 

unit

 

 

 

U1

 

 

 

U2

 

 

 

RC

 

 

 

Power supply Single-phase 230 / 208 V

Outdoor unit

 

 

L1 L2

1

2

G U1 U2

powerline

60V,Hz

 

 

Ground

 

 

 

Inter-unit

230 / 208

 

 

1

 

 

 

2

 

 

 

Indoor

 

 

 

unit

 

 

 

U1

 

 

 

U2

 

 

 

RC

 

 

 

Remote controller wiring

WHT

BLK

(Field supply)

1 2

 

(Optional)

 

Wired remote controller

Fig. 6-6a

(Wiring procedure)

Remote controller crossover wiring for group control

(1)Connect the remote controller to the indoor unit remote controller wiring.

Use the remote controller connection wire coming from the indoor unit, and field-supply wire and a wire joint to complete the connection as shown in Fig. 6-6b. The remote controller connection wire coming from the indoor unit includes a connector, therefore cut off the connector and use the wire joint to connect the wire from the remote controller.

(2)Connect the indoor units (U1, U2) and the outdoor units (1, 2).

Connect the other outdoor units and indoor units (with different refrigerant systems) in the same way. Connect the inter-unit control wiring to the indoor units (U1, U2) for each refrigerant system.

(Inter-unit control wiring)

Indoor

 

Indoor

unit 1

 

unit 2

RC

 

 

RC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WHT BLK

12

(Optional)

Wired remote controller

Fig. 6-6b

Indoor

unit 3

RC

6

6-7

Page 195
Image 195