Panasonic R410A Outdoor unit maintenance remote control, Normal Display Operations and Functions

Models: R410A

1 198
Download 198 pages 33.93 Kb
Page 181
Image 181
 All units start/stop (Fig. 1) <Operation>

5. Outdoor unit maintenance remote control

5-3. Normal Display Operations and Functions

Normal display functions

Connect the special service checker wiring to the outdoor unit PCB. The connection is shown in the figure below.

RC (3P, blue)

PCB connector (3P, blue)  All units test run (Fig. 2) <Operation>

Special service checker wiring

Relay connector (2P, white)

Fig. 1Manual backgroundManual background Remote controller Assy

Outdoor unit PCB

*It is not necessary to disconnect the communications line in the inter-unit control wiring if it has already been connected at this time.

*Setting modes 1 and 2 can be used even when the outdoor unit is independent (when 1 maintenance remote controller is connected to 1 outdoor unit and automatic address setting for the indoor units has not been com- pleted).

*Displays the overall system status for that refrigerant system.

Manual background All units start/stop (Fig. 1) <Operation>

The Manual background button can be used to start and stop all the indoor units.

The LED turns ON when 1 or more indoor units is operating.

The LED blinks when an alarm has occurred at 1 or more indoor units during operation.

Manual background Switching between cooling/heating (Fig. 1) <Operation>

The Manual background button switches between heating and cooling modes.

The specifications are equivalent to the heating/cooling input that was present on earlier outdoor unit PCBs.

The display shows the operating mode of the indoor unit with the lowest number.

Manual background All units test run (Fig. 2) <Operation>

The Manual background button switches test run ON/OFF for all indoor units.

Press and hold for 4 seconds to turn ON.

“Test run” is displayed while the test run is in progress.

Conditions of test runs that are started from the unit remote controller are not displayed on the outdoor unit maintenance remote controller.